Air Unit - Level 0 L00
Hardware Compatibility
Liebert Units:
Challenger 3, Logicool, Modular Plus, LS400, Mini-Tower, System 4
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=0ff
Heating
40004
4
BS04_x
1=on / 0=0ff
Humidification
40005
5
BS05_x
1=on / 0=0ff
Dehumidification
40006
6
BS06_x
1=on / 0=0ff
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=0ff
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Discrete BACnet alarm objects available
use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Liquid Detected
40289:4
289:4
BA01_x:04
Change Filters
40289:5
289:5
BA01_x:05
High Temperature
40289:6
289:6
BA01_x:06
Low Temperature
40289:7
289:7
BA01_x:07
High Humidity
40289:8
289:8
BA01_x:08
Low Humidity
40289:9
289:9
BA01_x:09
Local Alarm 1
40289:10
289:10
BA01_x:10
High Water Humidifier Pan
40289:11
289:11
BA01_x:11
Local Alarm 2
40289:12
289:12
BA01_x:12
Local Alarm 3
40289:13
289:13
BA01_x:13
Local Alarm 4
40289:14
289:14
BA01_x:14