Temperature/Humidity Module THM
Hardware Compatibility
Liebert Units:
THM100
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature Sensor 1
40001
1
BS01_x
Humidity Sensor 1
40002
2
BS02_x
Temperature Sensor 2
40003
3
BS03_x
Humidity Sensor 2
40004
4
BS04_x
Temperature Sensor 3
40005
5
BS05_x
Humidity Sensor 3
40006
6
BS06_x
Temperature Sensor 4
40007
7
BS07_x
Humidity Sensor 4
40008
8
BS08_x
Temperature Sensor 5
40009
9
BS09_x
Humidity Sensor 5
40010
10
BS10_x
Temperature Sensor 6
40011
11
BS11_x
Humidity Sensor 6
40012
12
BS12_x
Temperature Sensor 7
40013
13
BS13_x
Humidity Sensor 7
40014
14
BS14_x
Temperature Sensor 8
40015
15
BS15_x
Humidity Sensor 8
40016
16
BS16_x
Alarm Points
Communications
40289:0
289:0
BA01_x:00
High/Low Temp Sensor 1
Alarm threshold determined by others
High/Low Humidity Sensor 1
Alarm threshold determined by others
High/Low Temp Sensor 2
Alarm threshold determined by others
High/Low Humidity Sensor 2
Alarm threshold determined by others
High/Low Temp Sensor 3
Alarm threshold determined by others
High/Low Humidity Sensor 3
Alarm threshold determined by others
High/Low Temp Sensor 4
Alarm threshold determined by others
High/Low Humidity Sensor 4
Alarm threshold determined by others