Air Unit Level 10 L10
Hardware Compatibility
Liebert Units:
Modular Plus, Deluxe System/3, Industrial Cooling Series
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
Dehumidification
40006
6
BS06_x
1=on / 0=off
Econ-o-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Alarm Points
Communications
40289:0
289:0
BA01_x:00
High Head Pressure 1
40289:1
289:1
BA01_x:01
High Head Pressure 2
40289:2
289:2
BA01_x:02
Loss of Airflow
40289:3
289:3
BA01_x:03
Standby Glycol Unit On
40289:4
289:4
BA01_x:04
Liquid Detected
40289:5
289:5
BA01_x:05
Change Filters
40289:6
289:6
BA01_x:06
High Temperature
40289:7
289:7
BA01_x:07
Low Temperature
40289:8
289:8
BA01_x:08
High Humidity
40289:9
289:9
BA01_x:09
Low Humidity
40289:10
289:10
BA01_x:10
Humidifier Problem
40290:0
290:0
BA02_x:00
No Water in Humidifier Pan
40290:1
290:1
BA02_x:01
Compressor 1 Overload
40290:2
290:2
BA02_x:02
Compressor 2 Overload
40290:3
290:3
BA02_x:03
Main Fan Overload
40290:4
290:4
BA02_x:04