Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 115

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 114
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 115 of 149
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Utility Status
Bypass Status
40024
24
BS24_x
0=not present / 1=present
Battery Test In Progress
Battery Time Remaining
40021
21
BS21_x
Countdown timer starts at 254
Alarm Points
Communications
40289:00
289:00
BA01_x:00
Bypass Failure
40289:01
289:01
BA01_x:01
Input Failure
40289:02
289:02
BA01_x:02
Battery Discharging
40289:03
289:03
BA01_x:03
Low Battery Reserve
40289:04
289:04
BA01_x:04
Output Overload
40289:05
289:05
BA01_x:05
Ambient Overtemperature
40289:06
289:06
BA01_x:06
Output Undervoltage
40289:07
289:07
BA01_x:07
Output Overvoltage
40289:08
289:08
BA01_x:08
Charger Failure
40289:09
289:09
BA01_x:09
Load On Bypass
40289:10
289:10
BA01_x:10
Utility Failed
40290:00
290:00
BA02_x:00
Setpoints (View)
None
Control Points (Set)
None
Trendable Points (Set)
Bypass Voltage A-N
Bypass Voltage B-N
Bypass Voltage C-N
Voltage In A-N
Voltage In B-N
Voltage In C-N
Voltage Out A-N
Voltage Out B-N
Voltage Out C-N
Current In A
Current In B
Current In C
Current Out A
Current Out B