Modbus Communications
Connectivity to SiteLink modules using Modbus
This design specification describes the Modbus communications protocol as supported by the SiteLink module. It
includes information on how to pass information to and from the SiteLink module via Modbus. It is also intended to
help facilitate answering questions regarding supported types, frame format, function code support etc.
Implementation Basics
Protocol controls the language structure or message format between devices in other words, the rules for
communication. The rules for communication include how master and slave devices initiate communications, as
well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of
the query and response cycles between master and slave devices.
The SiteLink module is configured to act as a slave device on a common network. The common network can be
point-to-point over EIA-232, where one master communicates to one slave device or in a multi-drop configuration
over EIA-485, where multiple slaves reside on a common wire or loop.
Documented write points can cause read errors if you attempt to read a write-only point. For example: an LAM air
unit has separate Setpoint View and Setpoint Set registers and if you read a write-to register it can and most likely
will result in a Modbus exception response. Do not include setpoint set registers in batch read commands as one
point read error will result in an exception response for the entire batch read.
Transmission Format
The SiteLink module supports both Modbus RTU (Remote Terminal Unit) and ASCII (American Standard Code for
Information Interchange) transmission modes. The SiteLink module has a choice of transmission medium, baud
rate, character parity and number of stop bits. See chart below.
Physical
Port
Transmission
Mode
Baud Rate
Data Bits
Parity Bits
Stop Bits
Default
EIA-232
DB9 DCE
RTU
9600
8
None
1
Yes
EIA-232
DB9 DCE
ASCII
1200
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No
EIA-485 2
or 4 wire
RTU or ASCII
1200
38.4kbd
(19.2kbd omit)
Configurable
Configurable
Configurable
No