Emerson Autochangeover Controllers AC8 Manual de usuario Pagina 57

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 56
Revision B.33 2/25/2011
Liebert Monitoring Group Development
Page 57 of 149
Point Availability
SiteScan
Modbus
Register
BACnet
Object
Notes:
Alarm Points (cont.)
Alarm V (Word cont.)
40293
BA5
Power On
-
ba77
Standby Mode
bit10
ba78
Power Off
bit11
ba79
Reheat Lockout
bit12
ba7a
Humidifier Lockout
bit13
ba7b
Compressor Lockout
bit14
ba7c
Compressor 2 Short Cycle
bit15
ba7d
Control Points (Write)
Unit On/Off
40349
bc01
Modbus - Set Bit0=off, Bit1=on
Humidifier Lockout
40349
bc01_2
Modbus - Set Bit4=off, Bit5=on
Reheat Lockout
40349
bc01_3
Modbus - Set Bit2=off, Bit3=on
Temp Setpoint
40350
bp1c
Temp Proportional Band
40350
bp1e
Scale *1000 (Modbus Only)
Temperature DeadBand
-
bp20
Humidity
40351
bp23
Humidity Proportional Band
40351
bp24
Scale *1000 (Modbus Only)
Humidity Dead Band
-
bp26
Auto-restart Delay Seconds
-
bp27
IR Flush Rate %
-
bp34
High Temp Setpoint
-
bp36
Low Temp Setpoint
-
bp38
High Temp Setpoint Sensor A
-
bp3a
Low Temp Setpoint Sensor A
-
bp3c
High Humidity Setpoint
-
bp3e
Low Humidity Setpoint
-
bp3f
High Humidity Setpoint Sens A
-
bp40
Low Humidity Setpoint Sens A
-
bp41
VFD Control Speed
40349
bp86
Modbus - Set Bits8-15=speed 50-100%
VFD Control Mode
40349
bp87
Modbus - Set Bit6=auto, Bit7=manual