Air Unit Advanced Microprocessor LAM
Hardware Compatibility
Liebert Units:
Challenger 3000. Deluxe System / 3, ICS, System 4 (Replaces L15 & L1A)
HiMod (LNA version) iCOM control using native IGM terminal 77/78
SiteScan Interface Modules:
SiteLink (All)
BMS interface Modules:
SiteLink (All)
Available Points
SiteScan Availability
Modbus
Register
BACnet
Instance
(Exec. 6
Modules)
BACnet
Instance
(Exec. B
Modules)
Notes:
Status Points (View)
Temperature
40001
1
BS01_x
Humidity
40002
2
BS02_x
Cooling
40003
3
BS03_x
1=on / 0=off
Heating
40004
4
BS04_x
1=on / 0=off
Humidification
40005
5
BS05_x
1=on / 0=off
De-humidification
40006
6
BS06_x
1=on / 0=off
Econ-O-Cycle
40007
7
BS07_x
1=on / 0=off
Stages
40008
8
BS08_x
% Capacity
40009
9
BS09_x
Unit Status (On / Off)
40018
18
BS18_x
1=on / 0=off
Alarm Points
Discrete BACnet alarm objects available
use auto-discover for this unit
Communications
40289:0
289:0
BA01_x:00
Local Off
40289:1
289:1
BA01_x:01
Remote Off
40289:2
289:2
BA01_x:02
High Head Pressure 1
40289:3
289:3
BA01_x:03
High Head Pressure 2
40289:4
289:4
BA01_x:04
Loss of Airflow
40289:5
289:5
BA01_x:05
Standby Glycol Unit On
40289:6
289:6
BA01_x:06
Liquid Detected
40289:7
289:7
BA01_x:07
Change Filters
40289:8
289:8
BA01_x:08
High Temperature
40289:9
289:9
BA01_x:09
Low Temperature
40289:10
289:10
BA01_x:10
High Humidity
40290:0
290:0
BA02_x:00
Low Humidity
40290:1
290:1
BA02_x:01
Humidifier Problem
40290:2
290:2
BA02_x:02
No Water in Humidifier Pan
40290:3
290:3
BA02_x:03