P/N 400508-01Revision: A2Date: August 23, 2000© EMERSON Motion Control, Inc. 2000FM-3 Programming Module Reference Manual

Pagina 2

viiirelevant safety legislation in the country of use.AC supply isolation deviceThe AC supply must be removed from the drive using an approved isolati

Pagina 3 - Reference Manual

86FM-3 Programming Module Reference ManualDriveOutput.2=OFFEndifIf (DriveInput.1=ON AND DriveInput.2=OFF) Then‘Turn Outputs 1 On and 2 Off if Drive‘In

Pagina 4

87ProgrammingFor Count/NextThis instruction is used to execute section of code a specific number of times.Examples:For Count = 1 to 5Index.1.Initiate

Pagina 5 - Customer Service

88FM-3 Programming Module Reference ManualDwell For Time 1.000 ‘secondsLoopWait ForThis program flow instruction is used to halt program execution unt

Pagina 6

89ProgrammingWait For Time 1.000 ‘secondsDriveOutput.1=OFFWait For Index.AnyCommandCompleteLoopCall ProgramThis program flow instruction is used to c

Pagina 7 - Document Conventions

90FM-3 Programming Module Reference ManualFormulaThis program instruction can be used to enter a formula or assignment into a program. All FM-3 param

Pagina 8 - Reference Materials

91ProgrammingExample ProgramsOut and Return - SimpleDescription: Move out to an absolute position and returnIndex.2.Initiate ‘Absolute,Posn=10.000in,V

Pagina 9 - Safety Considerations

92FM-3 Programming Module Reference ManualRegistration Index to Place a Product on a Conveyor After Each LugRegistration Index (synchronized) to find

Pagina 10

93ProgrammingRotary Table with “Calibrated” Stop PositionsHome the axis, wait for an input and then index to 3 different stop positions (absolute posi

Pagina 11 - Table of Contents

94FM-3 Programming Module Reference ManualHome.0.Initiate ‘Sensor,Offset=1.000in,Vel=-5.0 in/sModuleEncoderInput.DefineHome=ON ‘Set the master positio

Pagina 12

95ProgrammingAuger Filler with Inputs to Adjust the Fill AmountIncremental indexes are used to squirt a specified amount of food product into a box.

Pagina 13 - Index 213

ixCustomer Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iiiRefere

Pagina 14

96FM-3 Programming Module Reference ManualSequence Learn and PlaybackThis example consists of three programs. The first program is used to learn 3 po

Pagina 15 - Introduction

97ProgrammingSubroutine for Jogging the Axis into the Desired Position (Program 1)‘Allow jogging until either the “Learn” input (ModuleInput.1)‘or the

Pagina 16 - Programming Module

98FM-3 Programming Module Reference ManualPlayback Program (Program 2)Home.0.Initiate ‘Sensor,Offset=0.000in,Vel=-10in/sDo While (TRUE) ‘Repeat until

Pagina 17 - Operational Overview

99Parameter DescriptionsThis section lists all programmable and feedback parameters available. The parameters are listed alphabetically by variable na

Pagina 18 - Keypad Interface

100FM-3 Programming Module Reference ManualAcceleration Time Scale AccelUnits.TimeScaleThis parameter is the time units for accel./decel. ramps. Poss

Pagina 19

101Parameter DescriptionsDefine Home DefineHomeThis destination is used to set the Commanded Position to the value specified in the DefineHomePosn var

Pagina 20 - How Jogging Works

102FM-3 Programming Module Reference ManualDrive Ambient Temperature DriveAmbientTempThis parameter should be set to reflect the ambient air temperatu

Pagina 21 - How Home Works

103Parameter DescriptionsDrive Input Raw DriveInput.#.RawThis displays the raw state of the digital input without debounce or forcing to override the

Pagina 22 - Home Sequence

104FM-3 Programming Module Reference ManualDrive Faults Bitmap Fault.DriveFaultsBitmapThis parameter is a 32-bit register which holds all of the drive

Pagina 23

105Parameter DescriptionsFault Counts Fault.#.CountsThe module stores the total number of times the specific fault has occurred since it was manufactu

Pagina 24 - Accuracy and Repeatability

xIndex View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Netwo

Pagina 25 - Sensor Min

106FM-3 Programming Module Reference Manualto the programmed speed in the same amount of time. It is used to hold motion without cancelling the move

Pagina 26 - Home Offset

107Parameter DescriptionsFollowing Error Limit FollowingErrorLimitThis parameter is used when the FollowingErrorEnable bit is set. This limit is compa

Pagina 27 - Specified

108FM-3 Programming Module Reference ManualCalculated Offset Home.#.Calculate

Pagina 28 - Home Examples

109Parameter DescriptionsLimit Distance Hit Home.#.LimitDistHitThis source is activated when the home sensor is not found before the Home Limit Distan

Pagina 29 - Offset Move

110FM-3 Programming Module Reference ManualTime Base Home.#.TimeBaseThe time base selects either realtime, which allows velocities, acceleration and d

Pagina 30

111Parameter Descriptionsdeactivate at the start of any deceleration or acceleration. During a synchronized index, this source could be active even w

Pagina 31 - Run at Velocity

112FM-3 Programming Module Reference ManualLimit Distance Hit Index.#.LimitDistHitThis source is activated when the registration sensor is not found b

Pagina 32 - Absolute vs. Incremental

113Parameter DescriptionsEnable Registration Window Index.#.RegistrationWindowEnableThis check box enables (if checked

Pagina 33 - Absolute Index

114FM-3 Programming Module Reference ManualInertia Ratio InertiaRatioThis specifies the load to motor inertia ratio. For example, a value of 25.0 spec

Pagina 34 - Incremental Indexes

115Parameter DescriptionsAt Velocity Jog.#.AtVelThis source activates when the particular jog has reached its target velocity. It deactivates when acc

Pagina 35

xiOnline Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187Specificati

Pagina 36 - How Communications Work

116FM-3 Programming Module Reference ManualVelocity Jog.#.VelThis parameter specifies the velocity used for jogging with the Jog.PlusActivate and Jog.

Pagina 37

117Parameter DescriptionsModbus Id Modbus.ModbusIdModbus ID # for this FM module and drive. Debounced

Pagina 38

118FM-3 Programming Module Reference ManualModuleOutput Enable Force ModuleOutput.#.ForceEnableIf ModuleOu

Pagina 39 - Setting Up Parameters

119Parameter Descriptionsdeactivate when it continues past the OnPosn. The important thing to remember is that the PLS.#.Status will be active if bet

Pagina 40 - Drive Encoder Output Group

120FM-3 Programming Module Reference Manualan absolute position of zero and ends at the RotaryRolloverPosn. For example in a rotary application a PLS

Pagina 41 - Motor Position Group

121Parameter DescriptionsFor example, with “Response” set to 50, the minimum time constant value is 1000/50 = 20 msec.Position Feedback PosnFeedbackFe

Pagina 42 - Master Feedback Group

122FM-3 Programming Module Reference ManualName Program.#.NameThis is a character string which the user can assign to an individual program. It allow

Pagina 43 - Torque Group

123Parameter DescriptionsInitiate Selector.SelectorInitiateWhen this destination is activated, the selector checks the status of all Selector.Select d

Pagina 44

124FM-3 Programming Module Reference ManualSoftware Travel Limit Plus Position SoftwareTravelLimitPlusPosnThe SoftwareTr

Pagina 45 - Scaling

125Parameter DescriptionsTorque Limit TorqueLimitThis is the level to which the TorqueCommand will be limited when the TorqueLimitEnable input functio

Pagina 47 - Acceleration Group

126FM-3 Programming Module Reference ManualUnits Name TorqueUnits.NameThe User can specify a torque unit name of up to 12 characters. Default is % Con

Pagina 48

127Parameter DescriptionsUnits Name VelocityUnits.NameIf the user wants the velocity units to have a different distance scaling than the distance unit

Pagina 49 - Master Distance Units

128FM-3 Programming Module Reference Manual• Index.#.PLSOffDistance• Index.#.PLSOnDistance• Index.#.RegistrationOffset• Index.#.RegistrationWindowEnd•

Pagina 50 - Master Acceleration Units

129InstallationBasic Installation NotesYou are required to follow all safety precautions during start-up such as providing proper equipment grounding,

Pagina 51

130FM-3 Programming Module Reference Manual Figure 55: Detaching the FM-3 from the Drive ConnectionsCautionDo not attach or detach the FM-3 when power

Pagina 52 - Limits Group

131InstallationSoftware InstallationEmerson Motion Control PowerTools® FM-3 software was designed for users who need access to all setup options and d

Pagina 53 - Rotary Group

132FM-3 Programming Module Reference Manual3. In the Run dialog box, type a:/setup, where a is the letter assigned to your 3.5" floppy drive.4.

Pagina 54 - Online Tab

133InstallationExiting the SoftwareChoose File from the menubar, then click Exit. If you are using the keyboard, press the shortcut key combination Al

Pagina 55

134FM-3 Programming Module Reference Manual

Pagina 56 - Assignments Tab (shown)

135Quick StartThe quick start guide provides information on the basic operation and functions of the FM-3. The quick start steps cover only the most b

Pagina 57

1IntroductionFM-3 is a compact and rugged function module that attaches to the front of the E Series drive. It provides eight digital input lines and

Pagina 58 - Assignments Tab

136FM-3 Programming Module Reference ManualTo select one of the individual setup views, click on the element in the hierarchy view. The element will

Pagina 59

137Quick Start Figure 58: User Units ViewNow setup the parameters in the Distance group on the User Units view. The Tab key is used to easily jump th

Pagina 60 - Online Status Tab

138FM-3 Programming Module Reference Manual Figure 59: Position ViewTo setup following error limit and software travel limits, fill out the following

Pagina 61

139Quick StartRamps ViewYou must setup the deceleration rate to be used on the Ramps view if a travel limit is encountered. Figure 60: Ramps ViewTrave

Pagina 62 - Position Error Integral Group

140FM-3 Programming Module Reference Manual Figure 61: Tuning ViewInertia Ratio - This parameter is the ratio between the reflected inertia of the loa

Pagina 63 - Time Constant

141Quick Start Figure 62: Making AssignmentsNotice that a Name can be associated to each input line. Each input line can also have a debounce time.Na

Pagina 64 - Faults View

142FM-3 Programming Module Reference Manual Figure 63: Output Lines ViewA name can also be given to each hardware output line. Figure 8 shows how to

Pagina 65 - PLS View

143Quick Start Figure 64: Jog Setup ViewJog Deceleration - Is the average deceleration rate used when decelerating to zero speed or to the new target

Pagina 66 - Direction

144FM-3 Programming Module Reference Manual Figure 65: Home Setup ViewDeceleration - Is the average deceleration rate used to decelerate from the targ

Pagina 67 - Rollover Point

145Quick Start Figure 66: Index Setup View (Absolute Type)Indexes use the following parameters:Index Name - Is a 12-character string that gives a desc

Pagina 68 - Selector View

2FM-3 Programming Module Reference ManualThe FM-3 stores E Series drive setup parameters within the module itself. This allows you to transfer the FM-

Pagina 69

146FM-3 Programming Module Reference Manual Figure 67: Index Setup View (Incremental Type)Now that all of the motion parameters are setup, the jogs an

Pagina 70 - Assignments

147Quick Start Figure 68: Program ViewThe window in the middle of the view allows selection from a list of Program Flow and Motion instructions. To i

Pagina 71 - Assignments View

148FM-3 Programming Module Reference Manual Figure 69: Program View (Expanded)A comment is automatically inserted after the index instruction, which s

Pagina 72 - Deleting An Assignment

149Quick StartExample Application Start Up Figure 70: Example SystemIn order to make the setup easier to understand in this guide, the guide will use

Pagina 73 - Assignment Polarity

150FM-3 Programming Module Reference Manualselects three digits allowing resolution of 0.001 Inches on all distance variables. Use the spinner window

Pagina 74 - Input Lines View

151Quick Start Figure 71: Assignments ViewThe Input Lines view shows all of the assignments that have been made to the Inputs group of Sources. After

Pagina 75 - Output Lines View

152FM-3 Programming Module Reference Manual Figure 72: Input Lines ViewNotice that a Name can be associated to each input line. Each input line can a

Pagina 76 - Jog View

153Quick StartHome SetupThe example application calls for setup of the following parameters:Home Reference –The example calls for a Home to Sensor; th

Pagina 77 - Jog Acceleration

154FM-3 Programming Module Reference ManualIndexes 0 and 1 are both Absolute type indexes and use the following parameters:Index Name - Is a 12-charac

Pagina 78 - Jog Sources and Destinations

155Quick Start Figure 75: Index Setup View (Incremental Type)Now that all of the motion parameters are setup, the jogs and indexes can be initiated th

Pagina 79

3Operational OverviewThis section provides a complete functional description of the FM-3. It is intended to provide you with a thorough understanding

Pagina 80

156FM-3 Programming Module Reference ManualWait For – This program instruction halts program execution until the expression becomes True. Once True,

Pagina 81

157Tuning ProceduresThe drive uses closed loop controllers to control the position and velocity Travel Limit of the attached motor. These position and

Pagina 82 - Home View

158FM-3 Programming Module Reference ManualTuning ProcedureOnce the initial setup has been completed, you can run the system to determine if the level

Pagina 83

159Tuning Procedures3. Enter the inertia value calculated into the Inertia Ratio parameter.4. Set the Line Voltage to the applied voltage (default is

Pagina 84 - End of Home Position

160FM-3 Programming Module Reference ManualTuning ParametersInertia RatioInertia Ratio specifies the load to motor inertia ratio and has a range of 0.

Pagina 85 - Home Sources and Destinations

161Tuning ProceduresIf the value entered is higher than the actual, system oscillation is likely. If the value entered is lower than the actual a more

Pagina 86 - Index View

162FM-3 Programming Module Reference Manualactual inertia, velocity error during ramping will be reduced but not eliminated. If the Friction parameter

Pagina 87

163Tuning ProceduresInitial Test SettingsWhen running the tests outlined in this section, the motor and drive must be operational so you will need to

Pagina 88 - PLS Off Point

164FM-3 Programming Module Reference ManualIf your application has less than a 10:1 inertia mismatch, the default parameter settings will be acceptabl

Pagina 89 - Registration Parameters

165Tuning Procedures3. Repeat Step 1 using a velocity at least two times the low speed.4. While at speed, note the Torque Command Actual value (TCH).5

Pagina 90

4FM-3 Programming Module Reference Manual Figure 3: Hierarchy ViewThe “Hierarchy View” (shown above) contains expandable groups of parameters. The gr

Pagina 91 - Destinations

166FM-3 Programming Module Reference Manual• If your application has a very limited range of motion, it is recommended that you use a position control

Pagina 92 - Index.#.Sensor Trigger

167Tuning ProceduresTd = (unsigned) percent continuous torque required during deceleration ramping (0 - 300)Vm = motor constant value from Table 18 be

Pagina 93 - Modbus View

168FM-3 Programming Module Reference ManualMotor Drive VmPercent Continuous/volt Scaled Torque Command Output (default))RPM /volt Scaled Velocity Comm

Pagina 94

169Diagnostics and TroubleshootingDiagnostic DisplayThe diagnostic segment display on the front of the drive shows drive status, FM-3 status, and faul

Pagina 95 - Wait For InPosn

170FM-3 Programming Module Reference ManualFault CodesA number of diagnostic and fault detection circuits are incorporated to protect the drive. Some

Pagina 96

171Diagnostics and TroubleshootingInvalid Configuration Button or Input Yes Invalid ConfPower Module Button or Input Yes Power Module High DC Bus But

Pagina 97 - Jog.PlusInitiate

172FM-3 Programming Module Reference ManualFault DescriptionsFlash InvalidThis fault indicates that the firmware checksum has failed. Use the Tools Pr

Pagina 98

173Diagnostics and TroubleshootingInvalid ConfigurationThe FM was not on this drive during its previous power-up and it is not known if the setup data

Pagina 99 - Program Flow Instructions

174FM-3 Programming Module Reference ManualEncoder HardwareIf any pair of encoder lines are in the same state, an encoder line fault is generated. The

Pagina 100

175Diagnostics and TroubleshootingFM-3 Specific Fault Descriptions Figure 78: FM-3 display is used to display drive and FM-3 faultsTraj FaultThis faul

Pagina 101

5Operational Overviewinformation. The four arrow keys are used to navigate through parameter groups, select a specific parameter to be modified, and t

Pagina 102

176FM-3 Programming Module Reference ManualBrake OperationMG motor brake operation is controlled by the Brake Release and Brake Control destinations.

Pagina 103

177Diagnostics and TroubleshootingAnalog OutputsThe drive has two 10 bit Analog Outputs which may be used for diagnostics, monitoring or control purpo

Pagina 104 - ModuleOutput.1 = ON

178FM-3 Programming Module Reference ManualDiagnostic Analog Output Test PointsThe DGNE cable was designed to be use with either an oscilloscope or a

Pagina 105 - Example Programs

179Diagnostics and Troubleshooting Figure 80: Diagnostic Cable (DGNE) Diagram10 Ohm10 OhmYellowBlack(GND)BlueD/AD/ADGNE CableCommandConnector (J5)DGNE

Pagina 106 - ‘Dist=50.000,Vel=1.000in/in

180FM-3 Programming Module Reference ManualDrive FaultsThe Active Drive Faults dialog box is automatically displayed whenever a fault occurs. There ar

Pagina 107 - Flying Cutoff/Shear

181Diagnostics and TroubleshootingThe terms below appear in the list the of common problems you might encounter when working with PowerTools software

Pagina 108

182FM-3 Programming Module Reference ManualProgramming Error MessagesThese Red Dot Error messages occur while you are working in the Program View. Whe

Pagina 109 - Programming

183Diagnostics and TroubleshootingError: A string variable can only be assigned a quoted text stringThe Variable is string. It only accepts types con

Pagina 110 - Sequence Learn and Playback

184FM-3 Programming Module Reference ManualError: Syntax error encounteredParser Error Message. The Parser can not understand your text sequence.Erro

Pagina 111

185Diagnostics and TroubleshootingError: The destination variable's resolution is less than the resolution of the numberYou attempted to assign a

Pagina 113 - Parameter Descriptions

6FM-3 Programming Module Reference Manual• INDEX (Index)• POSN (Position)• HOME (Home)• JOG (Jog)• RAMPS (Ramps)• SECUR (Security)Parameter ScreensAft

Pagina 114

186FM-3 Programming Module Reference ManualError: The Selection variable can only be assigned a Selection value.The destination variable only accepts

Pagina 115

187Diagnostics and TroubleshootingOnline Status IndicatorsGlobal Where Am I ButtonThe Program View, when online and executing a program or sequence of

Pagina 116

188FM-3 Programming Module Reference Manual

Pagina 117

189SpecificationsPower consumption: 3W from E Series drive power supply.I/O Supply Voltage: 10-30 VDC.Dimensions and ClearancesFunction Electrical Cha

Pagina 118

190FM-3 Programming Module Reference Manual2.6(66.0)

Pagina 119

191SpecificationsCable DiagramsCustomerSuppliedCableSync.InputSync.InputSync.InputSync.InputSync.OutputSync.OutputM FM FMFSNCE-xxx15', 25' o

Pagina 120

192FM-3 Programming Module Reference ManualSNCE-XXX CableSNCDD-001.5 CableAHBIJDCF38476512BGRD+5MMBAASHIELDGRD+5MMBBAA

Pagina 121

193SpecificationsSNCO-003 CableSNCI-003 Cable

Pagina 122

194FM-3 Programming Module Reference ManualSNCLI-003 Cable

Pagina 123

195SpecificationsCMDX-XXX CableNoteSome CMDX cables may have White/Yellow and Yellow/White wires in place of the White/Orange and Orange/White shown i

Pagina 124

7Operational OverviewEach jog has its own acceleration and deceleration ramp along with a specified velocity. Jogging has no distance parameter associ

Pagina 125

196FM-3 Programming Module Reference ManualCMDO-XXX CableNoteSome CMDO cables may have White/Yellow and Yellow/White wires in place of the White/Orang

Pagina 126

197SpecificationsCDRO-XXX Cable89242338371112341614152941926401817313343444127

Pagina 127

198FM-3 Programming Module Reference ManualTIA-XXX CableDDS-XXX Cable

Pagina 128

199SpecificationsTERM-H (Head) TerminatorTERM-T (Tail) Terminator NoteSee the "Multi-drop Communications" section for resistor values.

Pagina 129

200FM-3 Programming Module Reference ManualCMDS-XXX CableCMMS-XXX Cable

Pagina 130

201SpecificationsCFCS-XXX Cable

Pagina 131

202FM-3 Programming Module Reference ManualCFCO-XXX Cable

Pagina 132

203SpecificationsCFOS-XXX Cable

Pagina 133

204FM-3 Programming Module Reference ManualVendor Contact InformationSchaffner (AC Line Filters)(800) 367-5566 or (201) 379-7778 www.schaffner.comCoop

Pagina 134

205GlossaryµsMicrosecond, which is 0.000001 seconds.AAmps.AmplifierServo Drive.ARMSAmps Root Mean Squared (RMS).AxisThe full system to control in a si

Pagina 135

8FM-3 Programming Module Reference Manual Figure 6: Basic Home Function, ExampleThe figure above show a basic home function using a ball screw. This e

Pagina 136

206FM-3 Programming Module Reference ManualConfigurationThe user-created application. It can be saved as a disk file or downloaded to configure the FM

Pagina 137

207GlossaryFirmwareThe term firmware refers to software (i.e., computer programs) that are stored in some fixed form, such as read-only memory (ROM).F

Pagina 138

208FM-3 Programming Module Reference ManualInertiaThe property of an object to resist changes in rotary velocity unless acted upon by an outside force

Pagina 139

209GlossaryMost Significant BitThe bit in a binary number that is the most important or that has the most weight.msMillisecond, which is 1/1000th of a

Pagina 140

PLCProgrammable Logic Controller. Also known as a programmable controller, these devices are used for machine control and sequencing.Emerson Motion Co

Pagina 141 - Parameters Saved to NVM

211GlossaryTorqueThe moment of force, a measure of its tendency to produce torsion and rotation about an axis.UploadingThe transfer of a complete set

Pagina 142

212FM-3 Programming Module Reference Manual

Pagina 143 - Installation

213IndexSymbols+/- Limit, 174AAll "On", 174Analog Output, 177BBrake Operation and Wiring, 176CCable Diagrams, 191CDRO-XXX Cable, 197CFCO-XXX

Pagina 144 - Modbus Communications

214FM-3 Programming Module Reference ManualNNon-volatile Memory Invalid, 172OOver Speed Fault, 174PPower Stage Fault, 173Power-Up Self-Test Failure, 1

Pagina 146 - Starting the Software

9Operational OverviewPowerTools FM-3 allows selection of one of three different Home References: Sensor, Marker, or Sensor and Marker.SensorSelecting

Pagina 147 - Accessing Help

Since 1979, EMERSON Motion Control, a subsidiary of the Emerson Electric Company, has been a leader in the development and manufacturing of motion con

Pagina 148

10FM-3 Programming Module Reference ManualSensor and MarkerSelecting Sensor and Marker means the reference position is established using the first mar

Pagina 149 - Quick Start

11Operational Overview Figure 10: Sensor and Marker Home Reference Position Example 2The Home Sensor must be “On” for at least 1.6 msec to guarantee t

Pagina 150 - User Units View

12FM-3 Programming Module Reference ManualThe Specified Offset allows the user to choose an exact offset from the Home Reference.Once the home referen

Pagina 151 - Position View

13Operational OverviewTwo examples below show operation when the specified offset is greater or less than the calculated offset. This causes the axis

Pagina 152 - Velocity View

14FM-3 Programming Module Reference ManualHome Limit DistanceThis parameter places an upper limit on the incremental distance the motor will travel du

Pagina 153 - Tuning View

15Operational OverviewHome Sequence1. If on sensor then back off (if enabled)2. Search for sensor3. Search for marker4. Go to offset (2.0 Revs)5. Set

Pagina 154 - Step 3: Making Assignments

Information furnished by EMERSON Motion Control is believed to be accurate and reliable. However, no responsibility is assumed by EMERSON Motion Contr

Pagina 155 - Click and Hold

16FM-3 Programming Module Reference ManualExample 2: Rotary ApplicationThis example uses an external sensor and the motor’s encoder marker pulse to es

Pagina 156 - Jog Setup

17Operational Overview Figure 20: Home Velocity ProfileHow Indexes WorkAn index is a complete motion sequence that moves the motor a specific incremen

Pagina 157 - Home Setup

18FM-3 Programming Module Reference Manual Figure 22: Indexes ViewIndexes use acceleration and deceleration ramps which may or may not reach the speci

Pagina 158 - Index Setup

19Operational OverviewThe FM-3 calculates the distance required to move to the specified position from the current position.Absolute Index Figure 23:

Pagina 159

20FM-3 Programming Module Reference ManualIncremental IndexesAn incremental index will move the motor a specified distance in the + or - direction reg

Pagina 160 - Step 5: Creating a Program

21Operational Overviewalso be used to determine the validity of a registration trigger. If a registration trigger is received outside of the registra

Pagina 161

22FM-3 Programming Module Reference ManualExample 5: If the starting postion is 10° and the specified postion is 350°, a Rotary Plus index will travel

Pagina 162

23Operational OverviewCautionThe parameters will be sent to the FM-3 without stopping motion or disabling the drives. Because of this, it is importan

Pagina 163 - Home Prox

24FM-3 Programming Module Reference Manual

Pagina 164 - Making Assignments

25Setting Up ParametersSetup ViewThe Setup View contains all of the primary system setup parameters. These parameters must be setup prior to using you

Pagina 165

ii© EMERSON Motion Control, Inc. 2000Part Number: 400508-01Revision: A2Date: August 2000Printed in United States of AmericaInformation in this documen

Pagina 166

26FM-3 Programming Module Reference ManualTarget Drive AddressThis is the Modbus address of the target drive to which you will download the configurat

Pagina 167

27Setting Up ParametersScaling parameter is set to a value higher than the motor encoder density, the drive encoder output density will equal that of

Pagina 168

28FM-3 Programming Module Reference ManualDrive Information GroupFirmware Part NumberDisplays the part number of the drive firmware you are using.Firm

Pagina 169

29Setting Up ParametersMaster VelocityThis displays the velocity of the master encoder in master units/second.Torque GroupTorque CommandThis displays

Pagina 170

30FM-3 Programming Module Reference ManualUser Units ViewThe User Units View is used to scale the desired application units into known values. All inf

Pagina 171 - Tuning Procedures

31Setting Up ParametersScaling A Characteristic Distance and Length must be established to allow the FM-3 to scale user units back to actual motor re

Pagina 172 - Tuning Procedure

32FM-3 Programming Module Reference ManualVelocity GroupEnable Separate Distance Units Check BoxIf checked, separate distance and velocity units, name

Pagina 173 - General Tuning Hints

33Setting Up ParametersAcceleration GroupTime Scale List BoxFrom this list box, select the acceleration timescale to be used for all real-time profile

Pagina 174 - Tuning Parameters

34FM-3 Programming Module Reference ManualMaster Units ViewMaster Units setup provides the setup parameters for use with synchronized motion. This set

Pagina 175 - Feedforwards

35Setting Up ParametersMaster InterpretationMaster Interpretation determines how the incoming pulses are seen to generate the synchronized motion comm

Pagina 176 - Line Voltage

iiiCustomer ServiceIt is EMERSON Motion Control’s goal to ensure your greatest possible satisfaction with the operation of our products. We are dedica

Pagina 177 - Initial Test Settings

36FM-3 Programming Module Reference ManualDecimal PlacesThe number of decimal places set in this parameter determines the number of digits after the d

Pagina 178 - Determining Friction

37Setting Up ParametersPosition ViewThe Position View allows you to set up and view the parameters related to drive positioning.See Figure 31. The lef

Pagina 179 - FV )100(=

38FM-3 Programming Module Reference ManualIn Position WindowThe absolute value of the Following Error must be less than or equal to this value at the

Pagina 180

39Setting Up Parametersactive. Absolute Position Valid is active upon successful completion of a home or the DefineHome destination is activated. To r

Pagina 181 - Ramp Units Conversion

40FM-3 Programming Module Reference ManualAssignments TabDisplays any assignments to functions on this view that have been made using the assignments

Pagina 182

41Setting Up ParametersVelocity ViewThe Velocity View allows the setup of feedrate override details.By selecting Velocity in the hierarchy view, the V

Pagina 183 - Diagnostic Display

42FM-3 Programming Module Reference ManualCautionUsing the Update to RAM to change the Feedrate Override will implement the changes instantly. Instant

Pagina 184 - Fault Codes

43Setting Up ParametersRamps ViewThe Ramps View contains all setup information for the global acceleration and deceleration profiles. By selecting Ram

Pagina 185

44FM-3 Programming Module Reference Manualramps use smoothing at the beginning and end of the ramp but have constant (linear) accel-eration rates in t

Pagina 186 - Fault Descriptions

45Setting Up ParametersTorque ViewThe Torque View allows you to edit torque level and limit parameters as well as view realtime torque values when onl

Pagina 187

ivNeed on-site help? EMERSON Motion Control provides service, in most cases, the next day. Just call EMERSON’s customer service center when on-site se

Pagina 188

46FM-3 Programming Module Reference ManualLimits GroupTorque LimitThis parameter sets the value to which the Torque Command will be limited when the T

Pagina 189

47Setting Up ParametersTuning ViewThe Tuning View allows you to modify tuning parameters based on specific application information. By selecting Tunin

Pagina 190 - Brake Operation

48FM-3 Programming Module Reference ManualFrictionThis parameter is characterized in terms of the rate of friction increase per 100 motor RPM. If esti

Pagina 191 - Analog Outputs

49Setting Up ParametersTime ConstantPosition Error Integral is a control term, which can be used to compensate for the continuous torque required to h

Pagina 192 - Analog GND

50FM-3 Programming Module Reference ManualFaults ViewThe Faults View displays any active faults. See Figure 36. The Faults tab has been selected in th

Pagina 193

51Setting Up ParametersPLS ViewThe PLS View allows users to define Programmable Limit Switches (PLS) for advanced machine operation. By selecting PLS

Pagina 194 - Error Messages

52FM-3 Programming Module Reference ManualSourceThe source of a PLS can be assigned to the motor axis (MotorPosnFeedback, MotorPosnCommand) or a maste

Pagina 195

53Setting Up ParametersFor example, a flying cutoff or flying shear application may use this feature to activate the PLS to fire the knife only when t

Pagina 196 - Programming Error Messages

54FM-3 Programming Module Reference ManualI/O Setup GroupThe I/O Setup group contains four views that control input and output functions as well as ot

Pagina 197

55Setting Up ParametersThe maximum number of select lines is eight. Once you have determined how many select lines you want, the assignments to these

Pagina 198

vDocument ConventionsManual conventions have been established to help you learn to use this manual quickly and easily. As much as possible, these conv

Pagina 199

56FM-3 Programming Module Reference ManualIf Selector.Select2 is active, Selector.Select1 is inactive, and Selector.Select0 is active, then the total

Pagina 200

57Setting Up ParametersThe E Series drive’s input and output lines can be accessed through the removable 10-pin I/O connector (J6), or through the 44-

Pagina 201 - Online Status Indicators

58FM-3 Programming Module Reference ManualCreating An Assignment: Various methods will tie a source (such as DriveInput.1) to a destination, such as I

Pagina 202

59Setting Up Parameters Figure 41: Tying a Source to a DestinationAssignment PolarityThe active state of an assignment can be programmed to be Active

Pagina 203 - Specifications

60FM-3 Programming Module Reference ManualRight Click MethodPosition the pointer over the specific assignment you with to change polarity for and clic

Pagina 204

61Setting Up ParametersNameYou can assign a descriptive name to each input and make the setup easier to follow. The length of the text string is limit

Pagina 205 - Cable Diagrams

62FM-3 Programming Module Reference Manual Figure 44: Output Lines ViewNamesDescriptive text names can be assigned to individual output lines to make

Pagina 206 - SNCDD-001.5 Cable

63Setting Up Parameters Figure 45: Jog TabJog NumberThis scroll box allows you to select between Jog0 and Jog1 setup views.Jog NameThis is a descripti

Pagina 207 - SNCI-003 Cable

64FM-3 Programming Module Reference ManualJog DecelerationThis is the deceleration ramp used when stopping this individual Jog. If S-Curve ramps are u

Pagina 208 - SNCLI-003 Cable

65Setting Up ParametersWhen this destination is activated, jogging motion will begin in the positive direction. The jog velocity is determined by whet

Pagina 209 - CMDX-XXX Cable

viSafety InstructionsGeneral WarningFailure to follow safe installation guidelines can cause death or serious injury. The voltages used in the product

Pagina 210 - CMDO-XXX Cable

66FM-3 Programming Module Reference Manual Figure 46: Jog Activation Figure 47: Jog Select DetailsIf the Jog direction is reversed, the Jog.#.Decel va

Pagina 211 - CDRO-XXX Cable

67Setting Up ParametersIf the device is jogging with the Jog.PlusActivate destination active and the Jog.MinusActivate destination activates, the moto

Pagina 212 - DDS-XXX Cable

68FM-3 Programming Module Reference ManualHome ViewThe Home is used in applications in which the axis must be precisely aligned with some part of the

Pagina 213 - TERM-T (Tail) Terminator

69Setting Up ParametersTime BaseSelects the Time Base for the home move velocity and acceleration/deceleration. Real-time and sync are the allowed sel

Pagina 214 - CMMS-XXX Cable

70FM-3 Programming Module Reference Manualas specified. If the specified offset is smaller than the calculated offset, the motor will decelerate to a

Pagina 215 - CFCS-XXX Cable

71Setting Up ParametersHome Sources and DestinationsSourcesHome.AbsolutePosnValidThis source is activated when a Home is successfully completed. It in

Pagina 216 - CFCO-XXX Cable

72FM-3 Programming Module Reference ManualDestinationsHome.#.InitiateThe Home.#.Initiate destination is used to initiate the home function. The Home i

Pagina 217 - CFOS-XXX Cable

73Setting Up ParametersIndex NumberThe Index Number parameter selects the index number with a scroll box.Index NameThe User can specify an Index name

Pagina 218 - Vendor Contact Information

74FM-3 Programming Module Reference ManualDecelerationThe Deceleration parameter specifies the deceleration value to be used during the index in user

Pagina 219 - Glossary

75Setting Up ParametersIf Index 1 is run, the Index.1.PLSStatus will activate when the position feedback reaches -4 Revs (or 4 Revs from the start of

Pagina 220

vii Safety ConsiderationsSafety PrecautionsThis product is intended for professional integration into a complete system. If you install the product in

Pagina 221

76FM-3 Programming Module Reference ManualWindow EndThis parameter defines the end of the Registration Sensor Valid Window relative to start position

Pagina 222

77Setting Up ParametersIndex.#.AcceleratingThis source is active while an index is accelerating to its’ target velocity. Once the index reaches the t

Pagina 223

78FM-3 Programming Module Reference ManualIndex.#.Sensor TriggerIf registration to Sensor is selected, when this destination activates, motor position

Pagina 224

79Setting Up ParametersNetwork GroupModbus ViewThe Modbus View is used to assign Modbus addresses to individual parameters. By selecting Modbus in the

Pagina 225

80FM-3 Programming Module Reference ManualA “New Assignment” dialog box will appear. This will automatically assign the next available modbus address,

Pagina 226

81ProgrammingMotion Programs are a series of indexes, homes and jogs that have been previously setup. You combine these with other programming steps t

Pagina 227

82FM-3 Programming Module Reference Manualacceleration ramp. The index will finish at velocity. The program then moves on to the next index. It smo

Pagina 228

83Programming Figure 53: Index Velocity Profile with Drive OutputsIndex.0.CompoundInitiate ‘Incremetal,Dist=5.000in,Vel=50in/sDriveOutput.1=ON

Pagina 229

84FM-3 Programming Module Reference ManualExamples:Jog.0.PlusInitiate ‘Vel=27.2in/sJog.1.PlusInitiate ‘Sync,Vel=1.000in/inJog.MinusInitiateThis progra

Pagina 230

85ProgrammingDwell For TimeThis motion instruction is used to pause program execution for a very precise amount of time. It operates as a motion inst