FM-3 Programming Module Reference Manual
In Position Window
The absolute value of the Following Error must be less than or equal to this value at the end
of an index in order for the InPosn destination to activate. This window is set in units specified
in the User Units View.
For example:
The In Position window is set to .0025 revs. At the end of an index, the following error
is calculated to be .0012 revolutions. Therefore, the InPosn source will activate.
In Position window is set to .001 inches. If at the end of an index, the following error is
calculated to be .0015 inches, then the InPosn source will not activate.
In Position Time
This is the amount of time in seconds that commanded motion must be complete and the
absolute value of the following error must be less than the In Position Window for the InPosn
source to activate. If set to zero (default), then InPosn will activate as soon as motion stops
and the following error is less than the In Position Window parameter.
Limits Group
Enable Following Error Check Box
Check this box to enable (or disable if not checked) the Following Error Limit. If enabled, a
fault will be generated if the absolute value of the following error ever exceeds the value in
the following error parameter. If disabled, a fault will never be generated.
Following Error
The Following Error is the difference between the Position Command and the Position
Feedback. It is positive when the Position Command is greater than the Position Feedback. If
the absolute value of the following error exceeds the value you enter here, the drive will
generate a Following Error Fault (F). All accumulated Following Error will be cleared when
the drive is disabled.
The Following Error Limit is defined in user units.
Enable Software Travel Limits Check Box
Check this box to enable (or disable if not checked) the software travel limits. If unchecked,
the software travel limits are not monitored.
Software Travel Limits
Software Travel limits can be used to limit machine travel. They are often setup inside the
hardware travel limits to add another level of security or protection from exceeding the
machines travel limits. The FM-3 constantly monitors the feedback position, and if this
position exceeds the values entered for Software Travel Limit + or -, then the drive will decel
to a stop. Software Travel Limits are not functional unless the Absolute PosnValid source is