At Velocity Jog.#.AtVel
This source activates when the particular jog has reached its target velocity. It deactivates
when accelerating or decelerating to another target jog velocity.
Command Complete Jog.#.CommandComplete
The Jog.#.CommandComplete source activates when the specific Jog completes its
deceleration ramp and reaches zero commanded speed. It deactivates when the specific Jog is
initiated again.
Command In Progress Jog.#.CommandInProgress
The Jog.#.CommandInProgress source is high throughout an entire jog profile. The bit goes
high at the start of a jog acceleration ramp, and turns off at the end of a jog deceleration ramp.
Decelerating Jog.#.Decelerating
This source turns on at the beginning of a jog deceleration ramp and turns off at the
completion of the ramp.
Deceleration Jog.#.Decel
This parameter is the average deceleration ramp for the specific jog.
Initiate Minus Jog.#.MinusInitiate
This is used inside a program to initiate a specific jog. When this bit is active, jogging motion
will be initiated in the negative direction at the specified jog velocity.
Initiate Plus Jog.#.PlusInitiate
This is used inside a program to initiate a specific jog. When this bit is active, jogging motion
will be initiated in the positive direction at the specified jog velocity.
Time Base Jog.#.TimeBase
The time base selects either realtime, which allows velocities, acceleration and deceleration
to be based on real time, or synchronized, which allows for an external synchronization
signal.