MONITORING
OpenComms NIC
USER MANUAL
Vista de pagina 0
1 2 3 4 5 6 ... 55 56

Indice de contenidos

Pagina 1 - OpenComms NIC

MONITORINGOpenComms NICUSER MANUAL

Pagina 2

Introduction4Table 2 SpecificationsElectrical RequirementsVoltage18 to 24VAC50/60 Hz, Single Phase12 to 36VDCPower 6VA maximumEnvironmental Conditions

Pagina 3 - TABLE OF CONTENTS

Installation52.0 INSTALLATIONThe OpenComms NIC card may be ordered as a factory-installed option, and it may be installed as a kit for field retrofit

Pagina 4

Installation62.3 User Connections for OpenComms NICThe OpenComms NIC can use simultaneous connections, sometimes requiring three user connections:• Pe

Pagina 5

Installation7Accessing the Configuration PortWhat you will need:• PC capable of running a terminal emulation application, such as Microsoft Windows® H

Pagina 6

Installation8the Enter key on your keyboard. This will initiate communications with the card and the following screen should be displayed.Figure 4 NIC

Pagina 7 - 1.0 INTRODUCTION

System Configuration93.0 SYSTEM CONFIGURATION3.1 DIP Switch SettingsA four-position DIP switch is provided, but no user configuration via DIP switches

Pagina 8 - 1.1 OpenComms Compatibility

System Configuration10Table 3 Service terminal navigationMain Menu1. System Information1.1 Name1.2 Contact1.3 Location1.4 Description2. Network Settin

Pagina 9 - [email protected]

System Configuration11System Information MenuThe System Information Menu seeks descriptive input to enable the unit to be identified. This data is rea

Pagina 10 - Table 2 Specifications

System Configuration12destination IP address, and the community name for that host. Up to 20 trap communities can be assigned. For Communities and Tra

Pagina 11 - 2.0 INSTALLATION

System Configuration13Auxiliary CommunicationsThe Auxiliary Communications Menu allows the user to set up the parameters necessary for Modbus communic

Pagina 13

Operation144.0 OPERATION4.1 SNMPThe OpenComms Network Interface Card supports “get,” “getnext,” “set,” “response” and “trap” packets of SNMP (Simple N

Pagina 14 - Installation

Operation154.3 RFC 1628 UPS MIBUPS units log alarms in the RFC 1628 UPS MIB. Traps for the UPS units are generated out of the RFC 1628 UPS MIB. There

Pagina 15 - 3.0 SYSTEM CONFIGURATION

Operation16[OIDALARMS]1.3.6.1.2.1.33.1.6.3.1:upsAlarmBatteryBad{}1.3.6.1.2.1.33.1.6.3.2:upsAlarmOnBattery{}1.3.6.1.2.1.33.1.6.3.3:upsAlarmLowBattery{}

Pagina 16 - System Configuration

Operation174.4 MIBThe Management Information Base (MIB) is a formal document declaring the specifics of the information supported by the SNMP implemen

Pagina 17 - System Information Menu

Operation184.8 DiagnosticsA number of LEDs are provided on the interface card to provide infor-mation for diagnostic purposes. The following table sum

Pagina 18 - Factory Settings Menu

Modbus Communications and Connectivity195.0 MODBUS COMMUNICATIONS AND CONNECTIVITYThis section describes the Modbus communications protocol as sup-por

Pagina 19 - Auxiliary Communications

Modbus Communications and Connectivity205.3 Physical ConnectionA Modbus network should consist of one, and only one, host client, and up to 255 slaves

Pagina 20 - 4.0 OPERATION

Modbus Communications and Connectivity21Figure 7 Exceeding maximum specificationsThe maximum specification may be exceeded if measures are taken to dr

Pagina 21 - 4.3 RFC 1628 UPS MIB

Modbus Communications and Connectivity225.4.2 Function Code SupportThe OpenComms NIC implements the following Modbus functions. However, integrators w

Pagina 22 - Operation

Modbus Communications and Connectivity235.4.6 Read Input Status (0x02)The input status block contains read-only status accessible to the users. It can

Pagina 23 - 4.7 System Reset

iTABLE OF CONTENTS1.0 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.1 OpenComms Compatibility . . . . . . . . . . . . .

Pagina 24 - 4.8 Diagnostics

Modbus Communications and Connectivity24the OpenComms NIC module primarily uses Function Code 3 (Read Holding Registers) and Function Code 6 (Preset S

Pagina 25 - 5.2 Transmission Format

NIC Setup and Testing256.0 NIC SETUP AND TESTINGThe NIC has a specific setup that must be in place before the card will function properly. There are j

Pagina 26 - 5.3 Physical Connection

NIC Setup and Testing266.2 Testing the Network“Ping” is a tool used to test the network. At the command prompt, type, “ping <address of card>”.

Pagina 27 - 5.4 Modbus Slave Functions

NIC Setup and Testing27Then, select number 2 for Display/Modify Communities. Verify that the IP Addresses listed are valid for your network. Verify th

Pagina 28 - 5.4.2 Function Code Support

Firmware Updates287.0 FIRMWARE UPDATESThe firmware in the OpenComms NIC card can be updated to take advantage of the latest release of software that m

Pagina 29 - Modbus Packet Formats

Firmware Updates297.2 Establishing Communication—Service Terminal Settings1. Launch HyperTerminal. Once you see the following screen, select Cancel.2.

Pagina 30 - 5.5 RTU Framing Examples

Firmware Updates307.3 Firmware Update Procedure1. After the communication settings are adjusted, press the Enter key on your keyboard. This will initi

Pagina 31 - 6.0 NIC SETUP AND TESTING

Firmware Updates318. When the above prompt is displayed, start the file download process by selecting Transfer – Send File… from the HyperTerminal men

Pagina 32 - 6.4 SNMP Troubleshooting

Firmware Updates32Once the last file is downloaded, the screen at right will appear.Repeat Steps 2 through 4 to change the baud rate back to 9600 bps

Pagina 33 - 6.6 Modbus Troubleshooting

External Enclosures338.0 EXTERNAL ENCLOSURES8.1 Power ConnectionPower for the OpenComms Network card should be sourced from the supplied wall-plug tra

Pagina 34 - 7.0 FIRMWARE UPDATES

ii5.4 Modbus Slave Functions . . . . . . . . . . . . . . . . . . . . . . . . 215.4.1 Data Type. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 35 - Settings

Retrofit Installation349.0 RETROFIT INSTALLATION9.1 Environmental InstallationRetrofit kits are designed specifically for individual units. Consult yo

Pagina 36 - 7.3 Firmware Update Procedure

Retrofit Installation35Figure 11 Deluxe System 3 chilled water control cavityFigure 12 ICS control cavityP25P43TB1TB2 - Connects to screw terminals 77

Pagina 37 - Firmware Updates

Retrofit Installation36Figure 13 Challenger installation locationThe OpenComms Network card mounts on the Challenger’s L-plate.P25P43TB1TB2 - Connects

Pagina 38

Retrofit Installation379.2 System Wiring (SM, AM, AG Microprocessors)Two wiring harnesses are included with the retrofit kit, one for the power connec

Pagina 39 - 8.0 EXTERNAL ENCLOSURES

Retrofit Installation389.3.2 Communication Connection (SM, AM, AG Microprocessor)The second wiring harness provided (p/n 159083G1) has a connector fit

Pagina 40 - 9.0 RETROFIT INSTALLATION

Retrofit Installation399.4.1 System Wiring (Himod)Two wiring harnesses are included with the retrofit kit, one for the power connection and the second

Pagina 41 - Figure 12 ICS control cavity

Retrofit Installation409.6 Emerson Network Power (CEMS100 / LECS15)The kit includes a special cable to allow simple interconnection between the contro

Pagina 42

Retrofit Installation41Figure 15 NPower UPS NIC installationPower Supply BoardOption SectionSiteScan IFMOpenComms NIC location (see detail)Control Doo

Pagina 43 - Microprocessors)

Retrofit Installation429.9 7200 UPSRetrofit Kits are designed specifically for individual units. Consult your local sales / service representative for

Pagina 44 - 9.4 Himod (LNA)

Retrofit Installation43Figure 16 7200 UPS NIC installationLogic Operator BoardNetworkInterface Card

Pagina 45 - 9.5 Mini-Mate2

iii9.3 Power Connection (SM, AM, AG Microprocessors). . . . 379.3.1 Power Connection (Level 0 and Level 10Microprocessors) . . . . . . . . . . . . .

Pagina 46 - 9.8 Npower

Retrofit Installation449.10 HiPulse UPSRetrofit Kits are designed specifically for individual units. Consult your local sales / service representative

Pagina 47

Retrofit Installation45Figure 17 HiPulse installation

Pagina 48 - 9.9 7200 UPS

Retrofit Installation469.11 Static Switch2Retrofit kits are designed specifically for individual units. Consult your local sales / service representat

Pagina 49 - Retrofit Installation

Retrofit Installation47Figure 20 STS2 NIC installation, 100 - 600A units9.12 STSRetrofit kits are designed specifically for individual units. Consult

Pagina 50 - 9.10 HiPulse UPS

Retrofit Installation48

Pagina 52 - 9.11 Static Switch2

Technical Support/ServiceWeb Sitewww.liebert.comMonitoring800-222-5877monitoring@liebert.comOutside the US: 614-841-6755Single-Phase UPS800-222-5877up

Pagina 53 - 9.12 STS

ivFIGURESFigure 1 Typical installation of OpenComms NIC card . . . . . . . . . . . . . . . 1Figure 2 Connections . . . . . . . . . . . . . . . . . . .

Pagina 54

Introduction11.0 INTRODUCTIONThe OpenComms NIC Card transforms Liebert units into manageable nodes within your Network, NMS, and BMS systems.The OpenC

Pagina 55

Introduction21.1 OpenComms CompatibilityThe OpenComms NIC may be installed and used with these units:Environmental Units• Deluxe System3—Advanced Micr

Pagina 56 - USER MANUAL

Introduction3Retrofit Kits are designed specifically for individual units. Consult your local Emerson and Liebert sales representative for pricing, pa