Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
6-14
EDDL Trending of Mean
and Standard Deviation
Once the SPM has been enabled, the EDDL user interface allows for easy
viewing and trending of mean and standard deviation. To open up the trending
screen, go to
Service Tools > Trends > SPM and click the desired “Process Monitor #”
button
The EDDL Screen will show an on-line trend of mean and standard deviation,
along with the baseline values, percent change, and detection limits
(Figure 6-11).
Figure 6-11. EDDL Trend of
Mean and Standard Deviation
Note that data shown on the EDDL trends are not stored in a process
historian or other database. When this screen is closed, all of the past data in
the trends plots are lost. See “Trending SPM Data in DeltaV” on page 6-14 for
configuring SPM data to be stored in a historian.
Trending SPM Data in
DeltaV
Refer to “Trending Statistical Values in Control System” on page 6-10 for
general information about accessing the SPM data through the AI and MAI
function blocks. This section shows a specific example of how SPM Data can
be accessed within the DeltaV host system, saved into the process historian,
and used to generate a process alert.
In DeltaV Control Studio, add an AI function block, and assign it to one of the
AI function blocks in the 3051S Device. Set the CHANNEL to one of the valid
SPM channel values from Table 6-1 on page 6-11. For example, set the
CHANNEL to 13 for SPM1 Standard Deviation, as shown in Figure 6-12.