Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
B-8
Transmitter with MultiVariable
Sensor Module
Ambient Temperature Effect
Process Temperature RTD
Interface
(1)
Mounting Position
Effects
Differential Pressure and Static Pressure (3051SMV_ _1 or 2)
Models Classic MV
Per 50 °F (28 °C)
Ultra for Flow
-40 to 185 °F (-40 to 85 °C)
DP Ranges 2-3 ±(0.0125% URL + 0.0625% span)
from 1:1 to 5:1;
±(0.025% URL + 0.125% span) for >5:1
±0.13 reading up to 8:1 DP turndown
from URL;
±[0.13 + 0.0187(URL/Reading)]%
reading to 100:1 DP turndown from URL
DP Range 1 ±(0.1% URL + 0.25% span)
from 1:1 to 50:1
Not available
AP & GP ±(0.0125% URL + 0.0625% span)
from 1:1 to 10:1;
±(0.025% URL + 0.125% span) for >10:1
±(0.009% URL + 0.025% span)
from 1:1 to 10:1;
±(0.018% URL + 0.08% span) for >10:1
Liquid Level Transmitter
3051S_L
Ultra Classic
See Instrument Toolkit See Instrument Toolkit
Process Temperature (3051SMV_ _1 or 3)
(1)
Classic MV
Per 50 °F (28 °C)
Ultra for Flow
-40 to 185 °F (-40 to 85 °C)
±0.39 °F (0,216 °C) per 50 °F (28 °C) ±0.39 °F (0,216 °C) per 50 °F (28 °C)
(1) Specifications for process temperature are for the transmitter portion only. The transmitter is compatible with any Pt 100 (100 ohm platinum) RTD. Examples
of compatible RTDs include Rosemount series 68 and 78 RTD Temperature Sensors.
Line Pressure Effect
(1)
3051S_CD
3051SMV (DP Measurement Only)
Ultra and Ultra for Flow Classic and Classic MV
Zero Error
(2)
Range 2-3 ± 0.025% URL per 1000 psi (69 bar) ± 0.05% URL per 1000 psi (69 bar)
Range 0 ± 0.125% URL per 100 psi (6,9 bar) ± 0.125% URL per 100 psi (6,9 bar)
Range 1 ± 0.25% URL per 1000 psi (69 bar) ± 0.25% URL per 1000 psi (69 bar)
Span Error
(3)
Range 2-3 ± 0.1% of reading per 1000 psi (69 bar) ± 0.1% of reading per 1000 psi (69 bar)
Range 0 ± 0.15% of reading per 100 psi (6,9 bar) ± 0.15% of reading per 100 psi (6,9 bar)
Range 1 ± 0.4% of reading per 1000 psi (69 bar) ± 0.4% of reading per 1000 psi (69 bar)
(1) For zero error specifications for line pressures above 2000 psi (137,9 bar) or line pressure effect specifications for DP Ranges 4-5, see the 3051SMV
Reference Manual (document number 00809-0100-4803) or 3051S Reference Manual (document number 00809-0100-4801).
(2) Zero error can be removed by performing a zero trim at line pressure.
(3) Specifications for option code P0 are 2 times those shown above.
Models Ultra, Ultra for Flow, Classic and Classic MV
3051S_CD or CG
3051SMV_ _ 3 or 4
3051SF_3, 4, 7, or D
Zero shifts up to ±1.25 inH
2
O (3,11 mbar), which can be zeroed
Span: no effect
3051S_CA
3051S_T
Zero shifts to ±2.5 inH
2
O (6,22 mbar), which can be zeroed
Span: no effect