Reference Manual
00809-0200-4801, Rev CA
July 2010
D-3
Rosemount 3051S
Revised function blocks (comply w/ most recent ITK)
The Arithmetic, Characterizer and Integrator blocks had small changes made
to them to bring them in compliance to ITK 5.0 (One of the first devices to
pass this level).
Sensor status remains Uncertain when reading is beyond the sensor
limits (increased robustness)
Previous to this release when a pressure went beyond the sensor limits the
pressure status would go to BAD. For example; on a range 2 coplanar
transmitter the published upper sensor limit is 250in H2O although it will still
accurately read up to 277 inH2O and then continue to read much higher but
without much accuracy. In the previous release once the pressure went about
277 inH2O the status went to BAD which could initialize a safety action. Due
to customer demand, if the pressure goes above 277 inH2O the status now
goes to uncertain which allows the operator to determine whether that
pressure is bad or not.
The status does go to Bad when the absolute limit of the sensor is reached.