Emerson 3051S Especificaciones Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 240
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
Reference Manual
00809-0200-4801, Rev CA
July 2010
2-13
Rosemount 3051S Series
NOTE
It is important to know that Simulate is enabled only when the hardware
senses the switch changing from DISABLE to ENABLE. If the power is
removed with the switch in ENABLE, Simulate is not enabled. You must move
the switch from ENABLE to DISABLE and then back to ENABLE to be able to
use the Simulate software.
WIRING
Transmitter Wiring Wiring and power supply requirements can be dependent upon the approval
certification. As with all F
OUNDATION fieldbus requirements, a conditioned
power supply and terminating resistors are required for proper operation. The
standard 3051S pressure transmitter terminal block is pictured below. The
terminals are not polarity sensitive. The transmitter requires 9-32 Vdc to
operate. Type A F
OUNDATION fieldbus wiring 18 awg twisted shielded pair is
recommended.
NOTE
Avoid running instrument cable next to power cables in cable trays or near
heavy electrical equipment.
It is important that the instrument cable shield be:
- trimmed close and insulated from touching the transmitter housing
- continuously connected throughout the segment
- connected to a good earth ground at the power supply end
Figure 2-5.
FIELDBUS WIRING
DP
Trim shield and
insulate
Insulate
Shield
Connect Shield Back
to the Power Supply
Ground
Ground for
Transient
Protection
Minimize Distance
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 239 240

Comentarios a estos manuales

Sin comentarios