Reference Manual
00809-0200-4801, Rev CA
July 2010
C-7
Rosemount 3051S
Special conditions for safe use (x)
1. The 3051S HART 4-20 mA, 3051S F
OUNDATION fieldbus, 3051S Profibus and 3051S
FISCO are not capable of withstanding the 500V test as defined in clause 6.3.12 of IEC
60079-11. This must be taken into account during installation.
2. The terminal pins of the Types 3051S-T and 3051S-C must be protected to IP20
minimum.
N7 IECEx Type n
Certificate No.: IECExBAS04.0018X
Ex nC IIC T4 (T
a
= -40 °C to 70 °C)
Ui = 45 Vdc MAX
IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V insulation test required by Clause 8
of IEC 60079-15.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is specified. Once a device
labeled with multiple approval types is installed, it should not be reinstalled using any other
approval types. Permanently mark the approval label to distinguish it from unused approval types.
K1 Combination of E1, I1, N1, and ND
K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of E6 and I6
K7 Combination of E7, I7, and N7
KA Combination of E1, I1, E6, and I6
KB Combination of E5, I5, I6 and E6
KC Combination of E5, E1, I5 and I1
KD Combination of E5, I5, E6, I6, E1, and I1
Input Parameters
Loop / Power Groups
U
i
= 30 V HART / FOUNDATION fieldbus/ Remote
Display / Quick Connect / HART
Diagnostics
U
i
= 17.5 V FISCO
I
i
= 300 mA HART / FOUNDATION fieldbus/ Remote
Display / Quick Connect / HART
Diagnostics
I
i
= 380 mA FISCO
P
i
= 1.0 W HART / Remote Display / Quick
Connect / HART Diagnostics
P
i
= 1.3 W FOUNDATION fieldbus
P
i
= 5.32 W FISCO
C
i
= 30 nF SuperModule Platform
C
i
= 11.4 nF HART / HART Diagnostics / Quick
Connect
C
i
= 0 FOUNDATION fieldbus / Remote Display /
FISCO
L
i
= 0 HART / FOUNDATION fieldbus/ FISCO /
Quick Connect / HART Diagnostics
L
i
= 60 H Remote Display
RTD Assembly (3051SFx Option T or R)
U
i
= 5 Vdc
I
i
= 500 mA
P
i
= 0.63 W