Reference Manual
00809-0200-4801, Rev CA
July 2010
2-15
Rosemount 3051S Series
Figure 2-7. Optional LCD
Display
Setting Units Units for both the Sensor Transducer Block and the AI Block are set in the AI
Block. To change units:
Set the AI Block to OOS mode
Select XD_Scale.units_index
Select only one of the engineering units listed on page 3-10
Return AI Block to Auto mode
ZEROING TRANSMITTER Before operating the transmitter, perform a Zero Trim and set the Damping.
Refer to page 4-4 for zeroing procedures.
Damping The damping parameter in the Transducer Block may be used to filter
measurement noise. By increasing the damping time, the transmitter will have
a slower response time, but will decrease the amount of process noise that is
translated to the Transducer Block Primary Value. Because both the LCD and
AI Block get input from the Transducer Block, adjusting the damping
parameter will effect both blocks.
NOTE
The AI Block has it's own filtering parameter called PV_FTIME. For simplicity,
it is better to do filtering in the Transducer Block as damping will be applied to
primary value on every sensor update. If filtering is done in AI block, damping
will be applied to output every macrocycle.
ROSEMOUNT 305, 306
AND 304 MANIFOLDS
The Rosemount 305 is available in two designs: Traditional and Coplanar.
The traditional 305 Integral Manifold can be mounted to most primary
elements with mounting adapters in the market today. The Rosemount 306
In-Line Manifold is used with In-line transmitters to provide block-and-bleed
valve capabilities of up to 10000 psi (690 bar). The Rosemount 304 comes in
two basic styles: traditional (flange x flange and flange x pipe) and wafer. The
304 traditional manifold comes in 2, 3, and 5-valve configurations. The 304
wafer manifold comes in 3 and 5 valve configurations.