Advanced PIL
Configuration
PIL provides the ability for advanced users to fine-tune some of the algorithm
settings
PLINE_Relearn_Threshold
This adjusts the limit at which the PIL will automatically relearn new
baseline values if the process mean changes. By default, this threshold is:
2 inches of water for DP Range 1 (-25 to 25 inH
2
O) sensors
5 inches of water for DP Range 2 (-250 to 250 inH
2
O) sensors
1% of Primary Value Range for All Other Sensors
When PLINE_Relearn_Threshold is at 0 (default) the above values are
used for the relearn threshold. When a positive number is entered here,
this value (in % of Primary Value range) overrides the default relearn
threshold values. For example, if the sensor is type DP Range 3 (-1000 to
1000 inH
2
O), and PLINE_Relearn_Threshold is set to 2%, then PIL will
relearn if the mean changes by more than 20 inH
2
O.
NOTE
In software revisions 2.0.x and previous, the Relearn Thresholds for DP
Range 1 and DP Range 2 are fixed at the above default values. The
PLINE_Relearn_Threshold parameter affects the Relearn Threshold for only
the other sensors. In software revisions 2.1.x and later, the
PLINE_Relearn_Threshold affects the Relearn threshold for all sensor types.
PLINE_Auto_Relearn
This can be used to turn off the automatic relearning. If set to “Disabled”,
the PIL will not go back into learning mode, even if there is a large mean
change. In most cases, this parameter should be kept at “Enabled”
because without this check, a large change in a flow rate could also cause
a change in the standard deviation, triggering a false detection.
PLINE_Learn_Length
The length of time over which mean and standard deviation are calculated
during the Learning and Verification phases. Default is 5 minutes.
Allowable range is 1-45 minutes. If the process has a periodic change in
the mean over time (e.g. a slow oscillation), a longer learning cycle may
provide a better baseline.
PLINE_Detect_Length
The length of time over which mean and standard deviation are calculated
during the Detection Phase. Default is 1 minute. Allowable range is 1-45
minutes. This value should not be longer than the PLINE Learning Cycle.
A shorter value will in general allow a plugged impulse line to be detected
more quickly. However, if the process has a dominant cycling or oscillation,
this parameter should be set to longer than the period of oscillation.