Reference Manual
00809-0200-4801, Rev CA
July 2010
A-9
Rosemount 3051S
ANALOG INPUT (AI)
FUNCTION BLOCK
The Analog Input (AI) function block processes field device measurements
and makes them available to other function blocks. The output value from the
AI block is in engineering units and contains a status indicating the quality of
the measurement. The measuring device may have several measurements or
derived values available in different channels. Use the channel number to
define the variable that the AI block processes.
The AI block supports alarming, signal scaling, signal filtering, signal status
calculation, mode control, and simulation. In Automatic mode, the block’s
output parameter (OUT) reflects the process variable (PV) value and status.
In Manual mode, OUT may be set manually. The Manual mode is reflected on
the output status. A discrete output (OUT_D) is provided to indicate whether a
selected alarm condition is active. Alarm detection is based on the OUT value
and user specified alarm limits. Figure A-1 illustrates the internal components
of the AI function block, and Table A-3 lists the AI block parameters and their
units of measure, descriptions, and index numbers.
XD_
Scale
OUT_
Scale
Range Range
Manual
Auto
OOS
Standard
Deviation
Calculation
Alarm
Direction
OUT
OUT_D
ALM_SEL
ALARM_HYS
HI_HI LIM
HI_LIM
LO_LO LIM
LO_LIM
Status
Calc.
PV_FTIME
Direct
Indirect
Cutoff
Indirect
Filter
PV
Channel