Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
A-6
ADVISE_ALM 83 N/A Alarm indicating advisory alarms. These conditions do not
have a direct impact on the process or device integrity.
HEALTH_INDEX 84 1-100 100 None Read
Only
Parameter representing the overall health of the device, 100
being perfect and 1 being non-functioning. The value will be
set based on the active PWA alarms in accordance with the
requirements stated in “Device Alerts and Health Index
PlantWeb Implementation Rules”. Each device may
implement its own unique mapping between the PWA
parameters and HEALTH_INDEX although a default mapping
will be available based on the following rules.
HEALTH_INDEX will be set based on the highest priority
PWA *_ACTIVE bit as follows:
FAILED_ACTIVE: 0 to 31 – HEALTH_INDEX = 10
MAINT_ACTIVE: 27 to 31 – HEALTH_INDEX = 20
MAINT_ACTIVE: 22 to 26 – HEALTH_INDEX = 30
MAINT_ACTIVE: 16 to 21 – HEALTH_INDEX = 40
MAINT_ACTIVE: 10 to 15 – HEALTH_INDEX = 50
MAINT_ACTIVE: 5 to 9 – HEALTH_INDEX = 60
MAINT_ACTIVE: 0 to 4 – HEALTH_INDEX = 70
ADVISE_ACTIVE: 16 to 31 – HEALTH_INDEX = 80
ADVISE_ACTIVE: 0 to 15 – HEALTH_INDEX = 90
NONE – HEALTH_INDEX = 100
PWA_SIMULATE 85 Off/On (0-1) Off None Parameter that allows direct writes to PWA active parameters
and the detailed status bytes that activate the Plant Web
alerts. The simulate switch/jumper must be “ON” before
PWA_SIMULATE can be turned on.
0 = Simulation off
1 = Simulation on
Parameter Index Valid Range Initial Value Units Other Description