Reference Manual
00809-0200-4801, Rev CA
July 2010
A-13
Rosemount 3051S
LCD DISPLAY
TRANSDUCER BLOCK
Table A-4. LCD Display
Transducer Block Parameters
Parameter Index Valid Range Initial Value Units Other Description
ST_REV 1 0-255 The revision level of the static data associated with the
function block.
TAG_DESC 2 spaces N/A The user description of the intended application of the block.
STRATEGY 3 0 N/A The strategy field can be used to identify grouping of blocks.
ALERT_KEY 4 1-255 0 N/A The identification number of the plant unit.
MODE_BLK 5 O/S N/A The actual, target, permitted, and normal modes of the block.
BLOCK_ERR 6 E Read
Only
This parameter reflects the error status associated with the
hardware or software components associated with a block. it is
a bit string, so that multiple errors may be shown.
UPDATE_EVT 7 N/A Read
Only
This alert is generated by any change to the staic data.
BLOCK_ALM 8 N/A The BLOCK_ALM is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
TRANSDUCER_
DIRCTORY
9 N/A Read
Only
A directory that specifies the number and starting indicies of
the transducers in the transducer block.
TRANSDUCER_
TYPE
10 100 E Read
Only
Identifies the transducer that follows.
XD_ERROR 11 E Read
Only
Provides additional error codes related to transducer blocks.
COLLECTION_
DIRECTORY
12 N/A Read
Only
A directory that specifies the number, starting indicies, and DD
Item ID's of the data collections in each transducer block.
DISPLAY_
PARAM_SEL
13 Bit 0 – Bit 4 Bit 0 – DP1 E This will determine which Display Parameters are active.
Bit 0 = DP1
Bit 1 = DP2
Bit 2 = DP3
Bit 3 = DP4
Bit 4 = Bar Graph enable
BLK_TYPE_1 14 See Table 33 0x8001 E The enumerated block type for DP1’s block.
BLK_TAG_1 15 "TRANSDUC
ER"
N/A The tag of the block containing DP1.
PARAM_INDEX_
1
16 14 N/A The relative index of DP1 within its block. See Table 34
CUSTOM_TAG_1 17 spaces N/A The block description that is displayed for DP1.
UNITS_TYPE_1 18 1: Auto
2: Custom
3: None
1 E This parameter determines where the units for the display
parameter come from.
CUSTOM_UNITS
_1
19 spaces N/A This is the user entered units that are displayed when
UNITS_TYPE_1=Custom.
BLK_TYPE_2 20 See Table 33 0 E The enumerated block type for DP2’s block.
BLK_TAG_2 21 spaces N/A The tag of the block containing DP2.
PARAM_INDEX_
2
22 0 N/A The relative index of DP2 within its block. See Table 34
CUSTOM_TAG
_2
23 spaces N/A The block description that is displayed for DP2.
Vista de pagina 122