1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.98/106
44 BLACK-OUT
After the black-out is restored:
1. The instrument resores the same operating mode lost after the supply failure.
2. If active, the defrost is aborted.
3. All the timers and time parameters are reloaded.
4. The manual alarm is not reset.
45 INSTALLING AND MOUNTING
45.1 PANEL CUT- OUT
The instrument must be mounted on vertical panel, with panel cut-out 150x31mm, and screwed 2 screws 3 x 2mm, in between
distance 165mm. The IP65 can be reached with the gasket RG-L (opzionale).
The ambient working temperature range should be between 0÷60°C. Avoid locations subject to heavy vibration, corrosive gases or
excessive dirt. The same applies to the probes. Ensure ventilation around the instrument.
165
150
31
Ø3 x2
45.2 PLEXIGLASS PROTECTION BOTTOM OPEN
45.3 PLEXIGLASS PROTECTION TOP OPEN