1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.54/106
4. Push SET for 3 seconds when the label corresponds to the compressor to disable: CO1E - CO2E - CO3E - CO4E - CO5E -
CO6E. The top display shows the blinking En label, use the UP or DOWN key and change to diS (Compressor disabled) or
En (compressor enabled) then push SET to confirm, the display shows next item.
5. To exit the COEn function push MENU key or wait the timeout.
17.10 READ-OUT OF A COMPRESSOR NOT ENABLED
During the normal running condition a disabled compressor is displayed with a blinking label alternated with the measurement value of
the display.
If the compressor is disabled these the corresponding labels: C1dS = compressor 1 disabled…C6dS = compressor 6 disabled
The label C1dS…C6dS are available only if the corresponding compressor is configured.
17.11 READ-OUT OF THE COMPRESSOR DISCHARGE TEMPERATURE PROBE
The menu function allows to read-out the compressor temperature probes.
COdt FUNCTION shows the discharge temperatures
Label involved in Codt function: CO1t Compressor 1 discharge temperature… CO6t Compressor 6 discharge temperature
1. Use the UP or DOWN keys to select COdt
2. Push SET key: bottom display = CO1t, top display = temperature value of that probe.
3. Use the UP or DOWN kys to scroll the list: CO1t or CO2t or CO3t or CO4t or CO5t or CO6t
4. To exit the COEn function push MENU key or wait the timeout
ATTENZIONE
The labels Codt are available only if the corresponding compressor probe is configured.
The display resolution is 0.1°C until the read-out is 99.9, over 100°C it is 1°C.
17.12 READ-OUT OF THE RUNNING HOURS
This menu allows to shows all the time running hours of the compressors, supply fan and pumps.
Hour FUNCTION to show the controlled load consumption
Label involved in the Hour function:
CO1H Compressor 1 running hours .. CO6H Compressor 6 running hours.
EP1H Evaporator water pump or Supply fan running hours (air/air)
EP2H Support evaporator water pump running hours
CP1H Condenser water pump running hours
CP2H Support condenser water pump running hours
The labels are displayed only if the corresponding output is present and configured.
The running hours is displayed on the top display, the resolution is x 10 hours (eg 2 means 20 hours, 20 means 200hours)
Enter the function Menu
1. Use the UP or DOWN keys to select Hour
2. Push SET key: bottom display = above labels, top display = hours x10. The time
is on.
3. Use the UP or DOWN keys to scroll the list.
4. To exit the Hour function push MENU key or wait the timeout
17.13 RESET THE RUNNING HOUR
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CO1H, CO2H, CO3H, CO4H, CO6H, EP1H, EP2H,
CP1H, CP2H.
2. Push the SET keys for 3seconds: the top display shows the running hours blinking value, then it shows 0 to confirm the reset.
The next load label is automatically loaded.
To exit the Hour function push MENU key or wait the timeout
17.14 READ-OUT OF THE COMPRESSOR STARTS-UP
For each compressor is possible to show the number of starts-up.
COSn FUNCTION: number of starts-up of the compressor
Label involved in COSn function: C1S number of compressor 1 starts-up .. C6S number of compressor 6 starts-up
The labels are displayed only if the corresponding output is present and configured
The number of starts-up is displayed on the top display, the resolution is x 10 (eg 2 means 20 starts, 20 means 200starts)
Enter the function Menu
1. Use the UP or DOWN keys to select COSn.
2. Push SET one time: the label of the first load C1S is showed on the top display, the bottom display shows the number x10.
3. With UP or DOWN scroll the compressor list.
4. To exit the Hour function push MENU key or wait the timeout
17.15 RESET THE STARTS-UP NUMBER
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CS1, CS2, CS3, CS4, CS6.
2. Push the SET keys for 3seconds: the top display shows the running hours blinking value, then it shows 0 to confirm the reset.
The next load label is automatically loaded.
3. To exit the Hour function push MENU key or wait the timeout.