1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
dP 1 Default read-out of the top display 0 14
dP 2 Default read-out of the bottom display 0 17
dP 3 Default display read-out configuration top / bottom
0= Configurable
1= Top display: Evaporator IN, Bottom display: Evaporator OUT
2= Top display: Condenser IN, Bottom display: Condenser OUT
3=Top display: temperature/Condensing pressure, Bottom Display:
evaporating pressure
0 3
Display read-out of the remote terminals
dP4 Top display default read-out of the remote terminal_1
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel.
0 1
dP5 Top display default read-out of the remote terminal_2
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel.
0 1
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999
Configuration
Parameter Description min max M. u. Resolution
Unit Model
CF 1 Type of unit
0= Air / air Chiller
1= Air / water Chiller
2= Water / water Chiller
0 2
CF 2 Heat pump
0= no
1= Yes
0 1
CF 3 Motocondensing unit (not available)
0= no
1= si
0 1
Compressors
CF 4 Compressors number for circuit #1
1= 1
2= 2
3= 3
4= 4
0 4
CF 5 Compressors number for circuit #2
0= 0
1= 1
2= 2
3= 3
0 3
CF 6 Number of compressor parzialization
0= none
1= 1
2= 2
3= 3
0 3
Analog Inputs
CF 7 Pressure or temperature analogue input functioning
0 = Temperature / pressure NTC – 4÷20 mA :
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 4÷20mA
transducers.
1 = Pressure control with 4÷20 mA:
To control the evaporating and condensing pressures it is necessary a
4÷20mA transducer.
2 = Temperature / pressure NTC – 0÷5Vdc:
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers.
3 = Pressure control with 0÷5Vdc:
To control the evaporating and condensing pressures it is necessary a
ratiometric 0÷5Vdc transducer.
0 3
CF 8 PB1 Configuration
If configured as digital input
0
o 1
25
c63
CF 9 PB2 Configuration
If configured as digital input
0
o 1
25
c63
CF 10 PB3 Configuration
If configured as digital input
0
o 1
30
c63
CF 11 PB4 Configuration
If configured as digital input
0
o 1
30
c63
CF 12 PB5 Configuration
If configured as digital input
0
o 1
30
c63