1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.50/106
15.2 DEFAULT READ - OUT OF THE BOTTOM DISPLAY
To set the default value displayed on the bottom display:
1. Set the parameter dP03 = 0, it means configurable;
2. Select the dP02 parameter into the range 0..17 descripted here below:
PARAMETER
VALUE
DESCRIPTION
CORRESPONDING
LABEL
dP02=0 No display read out No label
dP02=1 NTC temperature probe of the evaporator water inlet Ein
dP02=2 NTC temperature probe of the evaporator water outlet 1 and 2
Out1 circuit 1
Out2 circuit 2
dP02=3 NTC temperature probe of the common evaporator water outlet Eout
dP02=4 NTC temperature probe of the condenser water inlet
CIn1 circuit 1
CIn2 circuit 2
dP02=5 NTC temperature probe of the common condenser water inlet Cin
dP02=6 NTC temperature probe of the condenser water outlet
Cou1 circuit 1
Cou2 circuit 2
dP01=7 NTC temperature probe of the common condenser water outlet Cout
dP02=8 NTC temperature probe of the dynamic external air setpoint Et
dP02=9 NTC temperature probe of the free cooling water inlet FCIn
dP02=10 NTC temperature probe of the free cooling external air value FCEt
dP02=11 NTC temperature probe of the remote terminal 1 trt1
dP02=12 NTC temperature probe of the remote terminal 2 trt2
dP02=13 NTC temperature probe of the combined defrost
dEF1 circuit 1
dEF2 circuit 2
dP02=14 NTC temperature probe of the condenser
Cdt1 circuit 1
Cdt2 circuit 2
dP02=15 Pressure probe of the condenser 4÷20mA - 0.5V
Cdt1 circuit 1
Cdt2 circuit 2
dP02=16 Pressure probe of the evaporator 4÷20mA - 0.5V
LP1 circuit 1
LP2 circuit 2
dP02=17 Clock
TOP DISPLAY: CUSTOM EXAMPLE
Parameter dP01=01. The default read out for the circuit 1 and the circuit 2 is the NTC probe value of the evaporator water inlet.
Parameter dP01=02. The default read out for the circuit 1 is the evaporator outlet 1 temperature, while for the circuit 2 is the evaporator
2 outlet temperature.
BOTTOM DISPLAY: CUSTOM EXAMPLE
Parameter dP02=03. The default read out for the circuit 1 and the circuit 2 is the NTC probe value of the evaporator water outlet.
Parameter dP02=14. The default read out for the circuit 1 is the condenser 1 temperature, while for the circuit 2 is the condenser 2
temperature.
15.3 FORCED READ - OUT OF THE TOP AND BOTTOM DISPLAY
To force the display read-out:
1. Set the dP03 parameter not equal to 0
2. Select the value range 1..3
These configurations allow to show together two temperatures or two pressures of the same circuit in order to have an easier reading of
the measurements:
Par. dP03 = 1
Top display: for both the circuits 1,2:
Evaporator water inlet, with the Ein label.
Bottom display: circuit 1:
Evaporator 1 water outlet, with the label OuT1