1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.92/106
41.32 B1RC B2RC RECOVERY DISABLED FROM HIGH CONDENSING
TEMPERATURE/PRESSURE IN CHILLER
Label on the display b1rC (recovery disabled message from circuit #1)
b2rC (recovery disabled message from circuit #2)
Origin In normal running condition when the temperature/pressure probe value is higher than the set rC06
Reset When the temperature/pressure probe value is lower than the rC06 –rC07(differential)
Unloading start after the time delay Par. rC08
Restart Automatic
Icona
Blinking
Action Alarm relay + buzzer OFF
41.33 B1PH - B2PH: PUMP DOWN STOP ALARM FROM PRESSURE SWITCH / LOW
PRESSURE SWITCH
Label on the display b1PH (Pump down stop alarm of the circuit 1)
b2PH (Pump down stop alarm of the circuit 2)
Origin Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops because of the timeout
CO39.
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump stops because of the
timeout CO39.
Reset From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 + CO38 (differential)
Restart Automatic – Manual and logged after AL21 events per hour (reset procedure in function menu).
Icona
Blinking
Action Alarm relay + buzzer ON when it becomes manual
41.34 B1PL - B2PL ALARM DURING THE PUMP DOWN START-UP FROM PUMP DOWN
PRESSURE SWITCH / LOW PRESSURE TRANSDUCER
Label o the display b1PL (pump down alarm in start-up of circuit #1)
b2PL (pump down alarm in start-up of circuit #2)
Origin Pump down pressure switch : CO36 = 1,2,3,4 and compressors start-up and digital input not active
for the time set in CO39
Pump down transducer: CO36 = 1,2,3,4, compressors start-up and the set CO37 is not reached in
the interval time CO39.
Reset From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 + CO38 (differential)
Restart Automatic - Manual and logged after AL21 events per hour if AL23=1 (reset procedure in function
menu).
If AL23 = 0 it is automatic and not logged.
Icona
Blinking
Action Alarm relay + buzzer ON when it becomes manual
41.35 C1MN - C2MN - C3MN - C4MN - C5MN - C6MN COMPRESSOR MAINTENANCE
Label o the display
C1Mn (Compressor #1 maintenance) –…C6Mn (Compressor #6 maintenance
)
Origin Compressor running hours > Hour counter setpoint
Reset Hour reset in function menu
Restart Manual
Icona
Blinking
Action Alarm relay + buzzer ON
Regulation
Action Only display warning messages
Loads Not changed
41.36 AEP1 - AEP2 PUMP/ SUPPLY FAN MAINTENANCE
Label o the display
AEP1 (Evaporator #1 pump maintenance)
AEP2 (Evaporator #2 pump maintenance)