1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
ES 17 Energy Saving differential in heat pump mode 0.0
0
25.0
45
°C
°F
Dec
int
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999
Compressors
Parameters Description min max udm Risoluzione
CO 1 Minimum compressor ON time after the start-up.
0 250
10
sec
10 sec
CO 2 Minimum compressor OFF time after the switching off.
0 250
10
sec
10 sec
CO 3 ON delay time between two compressors or compressor and valve. During
this time the led of the next resource is blinking.
1 250 Sec
CO 4 OFF delay time between two compressors or compressor and valve. During
this time the led of the next resource is blinking.
0 250 Sec
CO 5 Output time delay after the main power supply start-up to the unit.
All the loads are delayed in case of frequently power failures.
0 250
10
Sec
10 sec
Partialization (Capacity Control)
CO 6 Functioning (see Capacity Control)
0= With on/off steps
1= Continuous with steps and direct action
2= Continuous with steps and reverse action
3= Continuous with steps and direct total action
0 3
CO 7 Start-up with minimum compressor power / automatic start-unloading valve
0 = Only at the compressor start-up (Minimum power automatic start-
unloading valve off)
1= At the compressor start-up and during the termoregulation (Minimum
power / automatic start-unloading valve off)
2 = Only at the screw compressor start-up (Minimum power automatic start-
unloading valve off)
3= At the compressor start-up and during the termoregulation (Minimum
power / Unloading valve ON with compressor off)
0 3
CO 8 Relay ON time of the Solenoid valve Intermittent for screw compressor, with 0
the function is not enabled.
0 250 Sec
CO 9 Relay OFF time of the Solenoid valve Intermittent for screw compressor 0 250 Sec
Compressor start-up
CO 10 Kind of compressor start-up
0= Direct ( vedi avviamento compressors )
1= Part - winding
2= Star-delta
0 2
CO 11 If CO10= 1 part - winding start-up time. To change the time delay between the
two contactors of the two compressor circuits.
Se CO10= 2 Star-delta start-up time. To change the time delay between the
contactor of the line 1 and the contactor of the centre of the star. (see part –
winding /start-triangle functioning)
0 100
Dec.
di Sec
0.1 sec
CO 12 If CO10= 2 Time of Star-delta start. Time delay to turn off the centre star
contactor and to turn on the line 2 contactor (see Star-delta functioning)
0 50
Dec.
di Sec
0.1 sec
CO 13 By-pass gas valve start-up time / automatic start-unloading valve (capacity
step control)
0 250 sec
Rotating – Balancing – Compressors Thermoregulation
CO 14 Compressor rotation (See compressor rotation)
0 = Sequential
1 = Compressors rotation based on time running hours
2 = Compressors rotation based on number of starts-up
0 2
CO 15 Circuit balancing (See Circuit balancing)
0= Circuit saturation
1= Circuit balancing
0 1
Evaporator water pump
CO 16 Operative mode of the evaporator pump / supply fan (See Evaporator pump
function)
0= Not enabled (evaporator pump or supply fan).
1= Continuous. When the unit is running in Chiller or HP the pump or the
supply fan is running.
2= With compressor. When a compressor is running also the pump or the
supply fan is running.
0 2
CO 17 ON compressor delay after water pump / supply fan start-up (See water pump
functioning).
1 250 Min
CO 18 OFF delay evaporator water pump / supply fan after compressor switching
OFF. This delay is also active when the unit is turned in stand-by (See
evaporator water pump function).
0 250 Min
CO 19 Number of time running hours for pump rotation (See water pump group
function)
0 999 10Hr 10Hr
urenrjrjkvnm
Med