1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999
Recovery
Parameters description min max udm resolution
rC 1 Recovery modes
0 = not enabled
1 = 2 indipendent circuit
2 = both the circuit in parallel
0 2
rC 2 Delay time delay with step forced off 0 250 Sec
rC 3 Delay time delay with step forced off after the recovery valve activation 0 250 Sec
rC 4 Recovery minimum time 0 250 Min
rC 5 Minimum interval time between the end and the beginning of the next
recovery
0 250 Min
rC 6 Temperature setpoint to disable the recovery -30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 7 Temperature differential to restore the recovery 0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 8 Maximum time with recovery disabled (if temperature/pressure within rC6-
rC7)
0 250 Min
Pr1 Password 0 999
Pr2 Password 0 999
Pr3 Password 0 999
Alarms
Parameters Description min max m. u. Resolution
Low alarm
AL 1 Low pressure alarm delay from analog and digital input 0 250 Sec
AL 2 Low pressure alarm delay from digital input after compressor stop if the low
pressure switch is used for the pump down.
10 250 Sec
AL 3 Low pressure alarm setpoint from analogue input -30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
AL 4 Low pressure alarm differential from analogue input 0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
bar
psi
Dec
int
Dec
Int
AL 5 Maximum number of low pressure events from digital/analogue inputs:
Manual reset if AL05 = 0
Automatic reset if AL05 =16
From automatic to manual reset if AL05= 1..15
0 16
AL 6 Low temperature/pressure alarm during defrost
0= Not enabled
1= Enabled
0 1
AL 7 Low temperature/pressure alarm delay during defrost 0 250 Sec
AL 8 Low temperature/pressure alarm with unit in OFF or stand – by:
0 = Not enabled
1= Alarm enabled
0 1
High Alarm
AL 9 High temperature/pressure alarm from analogue input -30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
AL 10 High temperature/pressure alarm differential from analogue input 0.1
0
0.0
0
25.0
45
14.0
203
°C
°F
bar
psi
Dec
int
Dec
int
Oil Alarm
AL 11 Low oil pressure / level delay from digital input 0 250 Sec
AL 12 Minimum time for low oil pressure / level from digital input activation in normal
working condition.
0 250 Sec
AL 13 Maximum number of low oil pressure/level events:
Always manual reset if AL13= 0
Always automatic reset if AL13 =16
From automatic to manual reset if AL13 = 1..15
0 16
Flow alarm