1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Relay Outputs
CF 54 Configuration of RL1 0 -o1 c58
CF 55 Configuration of RL2 0 -o1 c58
CF 56 Configuration of RL3 0 -o1 c58
CF 57 Configuration of RL4 0 -o1 c58
CF 58 Configuration of RL5 0 -o1 c58
CF 59 Configuration of RL6 0 -o1 c58
CF 60 Configuration of RL7 0 -o1 c58
CF 61 Configuration of RL8 0 -o1 c58
CF 62 Configuration of RL9 0 -o1 c58
CF 63 Configuration of RL10 0 -o1 c58
CF 64 Configuration of RL11 0 -o1 c58
CF 65 Configuration of RL12 0 -o1 c58
CF 66 Configuration of RL13 0 -o1 c58
CF 67 Configuration of RL14 0 -o1 c58
Condensing proportional outputs
CF 68 Circuit 1 output signal:
0= 0 – 10Vdc
1= 4 ÷ 20mA
2= PWM for mono phase fan control board
0 2
CF 69 Circuit 2 output signal:
0= 0 – 10V
1= 4 ÷ 20Ma
2= PWM for mono phase fan control board
0 2
Uscite modulanti
CF 70 Proportional output 1
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
CF 71 Proportional output 2
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
CF 72 Proportional output 3
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
CF 73 Proportional output 4
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
Terminale remoto
CF 74 Remote Panel 1 configuration
0= Not enabled
1= with NTC ambient temperature sensor
2= without NTC ambient temperature sensor
0 2
CF 75 Remote Panel 2 configuration
0= Not enabled
1= with NTC ambient temperature sensor
2= without NTC ambient temperature sensor
0 2
CF 76 Offset of the NTC probe of the remote terminal # 1 -12.0
-10
12.0
53
°C
°F
Dec
int
CF 77 Offset of the NTC probe of the remote terminal # 2 -12.0
-10
12.0
53
°C
°F
Dec
int
Icon function
CF 78 Icon function
0=
chiller / heat pump
1=
chiller / heat pump
0 1
Chiller / heat pump selection mode