1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
37.1 OUTPUT STEP RELE’ CONDENSER FAN
Par FA01 = 2 ON/OFF step regulation
N° 1 circuit with 4 step of ventilation
Step regulation
OUT relè step n° 1 step n° 2 step n° 3 step n° 4
Out relè step n° 1 step N° 1 ON step N° 1 OFF step N° 1 OFF step N° 1 OFF
Out relè step n° 2 step N° 2 OFF step N° 2 ON step N° 2 OFF step N° 2 OFF
Out relè step n° 3 step N° 3 OFF step N° 3 OFF step N° 3 ON step N° 3 OFF
Out relè step n° 4 step N° 4 OFF step N° 4 OFF step N° 4 OFF step N° 4 ON
Par FA01 = 3 ON/OFF continuous step regulation
N° 1 circuito con quattro gradini di ventilazione
Continuous step regulation
OUT relè Gradino n° 1 Gradino n° 2 Gradino n° 3 Gradino n° 4
Out relè step n° 1 step N° 1 ON step N° 1 ON step N° 1 ON step N° 1 ON
Out relè step n° 2 step N° 2 OFF step N° 2 ON step N° 2 ON step N° 2 ON
Out relè step n° 3 step N° 3 OFF step N° 3 OFF step N° 3 ON step N° 3 ON
Out relè step n° 4 step N° 4 OFF step N° 4 OFF step N° 4 OFF step N° 4 ON
37.2 PWM OUTPUT FOR FAN CONTROL
If FA01=3 and the fan control boards are connected to the PWM outputs (TF1 and2) take note of the FA03 ,FA04 parameters.
The fan start-up is always made at the maximum speed for the time set in FA03, then the speed follows the probe value.
The F04 delay, in micro – seconds, allows to adjust the output for each kind of the fan motor.
If FA01=3, when the compressor starts-up and the proportional regulation requires to turn off the fan (cut-off), if FA14≠0 the fan is forced
at the minimum speed for the time set in FA14 itself. if FA14=0 the function is disabled.
37.3 CONDENSING UNIT: COMMON OR SEPARATE
FA05 defines the condenser unit
Par. FA05 type of condenser
0= Common condenser unit.
1= Separate condenser units.
If Pa FA05= 0 the outputs, configured as condensing fan control, will follow the same regulation algorithm.
The regulation includes:
• CHILLER mode: the maximum probe value compared between the temperature/pressure probe of the two circuits.
• HEAT PUMP (no evaporator probe configured) the minimum probe value compared between the condenser
temperature/pressure probe of the two circuits.
• HEAT PUMP (evaporator probe configured) the minimum probe value compared between the evaporator
temperature/pressure probe of the two circuits.
If par. FA05 = 1 and if the evaporating pressure probe are not configured, the fan output controls are separated and are controlled by
the condenser temperature/pressure probes. When the evaporator probes are configured, in heat pump the ventilation is controlled by
these transducers.
37.4 GRAPH: PROPORZIONAL REGULATION OF CONDENSER FANS