54 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Required Transmitter Configuration continued
6.5.1 Configuring the process variable
You can configure the process variables to be reported through the mA outputs.
Table 6-8 lists the process variables that can be assigned to the primary and secondary
mA outputs.
Note: Some transmitters can measure only mass flow and volume flow. See Table 6-3.
Note: If the enhanced density or petroleum measurement application is installed on your
transmitter, additional process variables will be available for assignment.
Note: The process variable assigned to the primary mA output is always the PV (primary variable)
defined for HART communications. You can specify this process variable either by configuring the
primary mA output or by configuring the PV (see Section 8.15.6). If you change the process variable
assigned to the mA output, the PV assignment is changed automatically, and vice versa.
If your transmitter has a secondary mA output, the process variable assigned to it is always the SV
(secondary variable) defined for HART communications. You can specify this process variable either
by configuring the secondary mA output or by configuring the SV (see Section 8.15.6). If you change
the process variable assigned to the mA output, the SV assignment is changed automatically, and vice
versa.
If your transmitter does not have a secondary mA output, the SV assignment must be configured
directly (see Section 8.15.6), and the value of the SV must be queried through an RS-485 connection,
read through the Communicator, or reported through burst mode.
Table 6-8 mA output process variable assignments
Process variable
(1)
(1) If the enhanced density application is enabled, enhanced density process variables are also available.
ProLink II code Communicator code Display code
Mass flow Mass Flow Mass flo MFLOW
Volume flow Vol Flow Vol flo VFLOW
Temperature Temp Temp TEMPR
Density Density Dens DENS
Temperature-corrected density
(2)
(2) Available only if the petroleum measurement application is enabled on your transmitter.
Dens at Ref TC Dens TCDEN
Temperature-corrected (standard) volume flow
(2)
Std Vol Flow TC Vol TCVOL
Drive gain Drive Gain Driv signl DGAIN
Average corrected density
(2)
(3)
(3) Requires rev3.3 or later of the transmitter software. Can be configured only with the display or with v1.2 or later of ProLink II
software.
Avg Corr Density AVE_D
Average temperature
(2)
(3)
Avg Temp AVE_T
• Model 1500 AN
• Model 1700 AN
• Model 1700 IS
• Model 2500 CIO
• Model 2700 AN
• Model 2700 IS
• Model 2700 CIO