Reference Manual00809-0100-4803, Rev DAApril 2013Rosemount 3051S MultiVariable™ Transmitter

Pagina 2

2Reference Manual00809-0100-4803, Rev DASection 1: IntroductionApril 2013Introduction1.2 Models coveredThe following 3051S MultiVariable Transmitters

Pagina 3

10Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.2 Safety messagesProcedures and inst

Pagina 4

11Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.3 Transmitter calibration4.3.1 Cali

Pagina 5 - Contents

12Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceData flow can be summarized in four ma

Pagina 6 - Table of Contents

13Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.3.3 Differential pressure sensor ca

Pagina 7 - 5Section 5: Troubleshooting

14Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceNoteSelect process variable calibratio

Pagina 8

15Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceFigure 4-3. Calibration - static pres

Pagina 9 - Section 1 Introduction

16Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceRecall factory trimThe Recall Factory

Pagina 10 - 1.3 Service support

17Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceProcess temperature upper and lower s

Pagina 11 - Section 2 Installation

18Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.3.6 Analog calibrationFigure 4-5. Ca

Pagina 12 - 2.2.1 Warnings

19Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceAnalog output loop testUnder the Anal

Pagina 13 - 2.4 Installation procedures

9Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationSection 2 InstallationOverview . . . . . . . . . . . . . . . .

Pagina 14 - 2.4.2 Mounting considerations

20Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.4 Transmitter functional testsFigure

Pagina 15 - Conduit entry threads

21Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.4.2 Configuring fixed process varia

Pagina 16 - Process flange orientation

22Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceFigure 4-7. Process variables - primar

Pagina 17 - 2.4.3 Mount the transmitter

23Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.6 Field upgrades and replacements4.

Pagina 18 - Flange bolts

24Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceUpgrading or replacing the housing ass

Pagina 19 - Mounting requirements

25Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceFigure 4-10. SuperModule connectorNot

Pagina 20 - 2.4.4 Process connections

26Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceInstall feature board in the plantweb

Pagina 21 - ROSEMOUNT 3051S / 3051 / 2051

27Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance4.6.4 LCD displayTransmitters ordered

Pagina 22 - Impulse piping considerations

28Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and MaintenanceNoteIf the installation uses a manifol

Pagina 23

29Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance5. Install the drain/vent valve.a. Ap

Pagina 24

10Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.2.1 WarningsFailure to follow these installation guidelines co

Pagina 25 - Surges/transients

30Reference Manual00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 2013Operation and Maintenance

Pagina 26 - Signal wire grounding

9Reference Manual 00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingSection 5 TroubleshootingOverview . . . . . . . . . . .

Pagina 27 - 2.4.7 Grounding

10Reference Manual00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingTable 5-1. Diagnostic message troubleshootingLCD Messages

Pagina 28

11Reference Manual 00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013Troubleshooting(LCD is blank) LCD Update Error The LCD is no longer powe

Pagina 29 - 304 WAFER

12Reference Manual00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingTable 5-2. Transmitter troubleshootingSymptom Corrective

Pagina 30

13Reference Manual 00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013Troubleshooting5.3 Measurement quality and limit statusThe 3051S MultiVa

Pagina 31

14Reference Manual00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingLow Limited – Indicates the current variable reading has g

Pagina 32

15Reference Manual 00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013Troubleshooting5.5 Measurement troubleshootingThe transmitter provides a

Pagina 33

16Reference Manual00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingSymptom Corrective ActionImpulse piping • Check for entrap

Pagina 34 - Installation

17Reference Manual 00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013TroubleshootingNoteThe following performance limitations may inhibit eff

Pagina 35 - Section 3 Configuration

11Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.3 Installation considerations2.3.1 GeneralMeasurement perform

Pagina 36 - 3.2 Safety messages

18Reference Manual00809-0100-4803, Rev DASection 5: TroubleshootingApril 2013Troubleshooting

Pagina 37

9Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataAppendix A Specifications and Reference

Pagina 38 - Connecting to a PC

10Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTotal performance(1)Models Ultra Classi

Pagina 39 - 3.4 Flow configuration

11Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataMultiVariable Flow performance(1)Mass,

Pagina 40 - Online and offline mode

12Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataDynamic PerformanceAmbient Temperature e

Pagina 41

13Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataLine Pressure effect(1)Mounting Positio

Pagina 42 - 3.4.4 Preferences

14Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataPower supply effectLess than ±0.005% of

Pagina 43

15Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.1.2 Functional specificationsRange an

Pagina 44

16Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataService3051SMV_P (Direct Process Variabl

Pagina 45

17Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataLoad limitations Maximum loop resistanc

Pagina 46 - 3.4.6 Fluid properties

12Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationIf the transmitter write protection switch is in the “ON” positi

Pagina 47

18Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference Data3051SMV_ _ 3: Differential Pressure &

Pagina 48

19Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTurn-On timePerformance within specific

Pagina 49 - 3.4.8 Save / send

20Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.1.3 Physical specificationsElectrical

Pagina 50

21Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataBoltsPlated carbon steel per ASTM A449,

Pagina 51 - Sending a saved configuration

22Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTable A-2. Transmitter option weightsOp

Pagina 52 - Natural gas

23Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.2 Dimensional drawingsDimensions are

Pagina 53

24Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataCoplanar Flange Mounting ConfigurationsP

Pagina 54 - Custom gas

25Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataPlantWeb Housing with Coplanar SuperMod

Pagina 55 - Custom liquid [Density (T)]

26Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTraditional Flange Mounting Configuratio

Pagina 56

27Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.3 Ordering informationA.3.1 Rosemount

Pagina 57 - Units of measure

13Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationNoteDo not rotate the housing more than 180 degrees without fir

Pagina 58

28Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTemperature InputStandard StandardN(6)No

Pagina 59

29Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataProcess Connection SizeMaterial TypeFla

Pagina 60 - 3.6.2 Alarm and saturation

30Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataOptions (Include with selected model num

Pagina 61

31Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataDrain/Vent ValveStandard StandardD5(13)

Pagina 62 - 3.6.3 Variable mapping

32Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataDigital DisplayStandard StandardM5 Plant

Pagina 63 - 3.6.4 LCD display

33Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.3.2 Rosemount 300SMV Housing KitTable

Pagina 64 - 3.6.5 Communication setup

34Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataExternal ground screw assemblyStandard S

Pagina 65 - Enabling burst mode

35Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.4 AccessoriesA.4.1 Rosemount Engineer

Pagina 66 - Multidrop communication

36Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.5 Exploded view diagramThe following d

Pagina 67 - Loop current mode

37Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataA.6 Spare PartsSensor ModulesSee Rosemo

Pagina 68

14Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationCover jam screwFor transmitter housings shipped with a cover jam

Pagina 69 - 3.7 Variable configuration

38Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataNickel-plated Carbon Steel 03151-9200-00

Pagina 70

39Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataNi Plated CS Adapters 03031-1300-0115Fl

Pagina 71

40Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataTraditional Flange Bracket KitsB1 Bracke

Pagina 72

41Reference Manual 00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference DataASTM A 453, Class D Grade 660 (set of 4

Pagina 73 - Time conversion example:

42Reference Manual00809-0100-4803, Rev DAAppendix A: Reference DataApril 2013Specifications and Reference Data

Pagina 74

9Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsAppendix B Product CertificationsApproved m

Pagina 75 - 3.7.2 Energy rate

10Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsB.4.1 Hazardous Locations CertificationsNor

Pagina 76

11Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsND ATEX Dust Certificate No.: BAS01ATEX130

Pagina 77 - Energy conversion example:

12Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsINMETRO certifications E2 INMETRO Flameproo

Pagina 78

13Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsIECEx certificationsI7 IECEx Intrinsic Saf

Pagina 79 - Configuration

15Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.4.3 Mount the transmitterFigure 2-4 illustrates a typical 305

Pagina 80

14Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsCombinations of certificationsStainless ste

Pagina 81 - 3.7.3 Totalizer

15Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsB.5 Installation drawingsB.5.1 Factory Mut

Pagina 82

16Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 83 - Totalizer conversion example:

17Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 84 - 3.7.4 Differential pressure

18Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 85 - 3.7.5 Static pressure

19Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 86 - 3.7.6 Process temperature

20Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsB.5.2 Canadian Standards Association (CSA)

Pagina 87 - 3.7.7 Module temperature

21Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 88 - 3.7.8 Analog output

22Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 89

23Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 90

16Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationTable 2-1. Mounting bracketsFlange boltsThe 3051S MultiVariable

Pagina 91 - (page 1)

24Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 92 - (page 2)

25Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product CertificationsB.5.3 GE / GM option NEMA 4X

Pagina 93

26Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 94

27Reference Manual 00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 95 - 3.8.5 475 Fast keys

28Reference Manual00809-0100-4803, Rev DAAppendix B: Product CertificationsApril 2013Product Certifications

Pagina 96 - Function Fast Key Sequence

Index-1Reference Manual 00809-0100-4803, Rev DAIndexApril 2013IndexAAddressChanging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 97

Index-2Reference Manual00809-0100-4803, Rev DAIndexApril 2013IndexPPiping, impulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 99 - 4.1 Overview

Reference Manual00809-0100-4803, Rev DAApril 2013Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_saleThe Emerson logo

Pagina 100 - 4.2 Safety messages

17Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationTable 2-2. Bolt installation torque valuesFigure 2-5. Common t

Pagina 102 - 4.3.2 Sensor trim overview

18Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationSteam flow measurement Place taps to the side of the line. Mou

Pagina 103 - Upper and lower sensor trim

19Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationTo install adapters to a Coplanar flange, perform the following

Pagina 104 - Last DP sensor trim point

20Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationImpulse piping considerationsThe piping between the process and

Pagina 105

21Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.4.5 Connect wiring and power upIt is recommended to use twist

Pagina 106

22Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationFigure 2-10. Transmitter wiringNoteInstallation of the transient

Pagina 107

23Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationFigure 2-11. 3051S MultiVariable RTD wiring connectionThree-wir

Pagina 108 - 4.3.6 Analog calibration

24Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationNoteGrounding the transmitter case using the threaded conduit co

Pagina 109 - Analog output loop test

25Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.4.6 Conduit electrical connector wiring (option GE or GM)For

Pagina 110 - April 2013

26Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationFigure 2-14. External ground connectionTable 2-3. External grou

Pagina 111 - 4.5 Process variables

27Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation2.5 Rosemount 305 and 304 ManifoldsThe Rosemount 305 Integral M

Pagina 112 - 4.5.2 All variables tab

Reference Manual 00809-0100-4803, Rev DARosemount 3051S MultiVariable TransmitterApril 20131Rosemount 3051S MultiVariable Transmitter.Read this manual

Pagina 113 - Field device labels

28Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationNoteIf replacing the o-rings, be careful not to scratch or defac

Pagina 114 - Remove the feature board

29Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationDrain/VentValveDrain/Vent ValveEqualize(closed)ProcessIsolate(o

Pagina 115 - Black Rubber V-Seal

30Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013InstallationFive-valve Natural Gas configurations shown:NoteDo not open the

Pagina 116 - 4.6.3 Terminal block

31Reference Manual 00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation3. Close the equalize valve on the high pressure (upstream) sid

Pagina 117 - 4.6.5 Flange and drain vent

32Reference Manual00809-0100-4803, Rev DASection 2: InstallationApril 2013Installation

Pagina 118

Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 20139ConfigurationSection 3 ConfigurationOverview . . . . . . . . . . . . . .

Pagina 119 - 4.6.6 SuperModule assembly

10Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.2 Safety messagesProcedures and instructions in this section

Pagina 120 - Operation and Maintenance

11Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.3 Engineering assistant installation3.3.1 Engineering assis

Pagina 121 - Section 5 Troubleshooting

12Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationConnecting to a PCFigure 3-1 shows how to connect a computer t

Pagina 122 - Troubleshooting

13Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.4 Flow configuration3.4.1 3051SMV engineering assistant 6.1

Pagina 124 - Symptom Corrective Actions

14Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationOnline and offline modeThe Engineering Assistant software can

Pagina 125

15Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration4. The Back button is used to step backward through the flow

Pagina 126

16Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-4. Engineering assistant device connection screen3.4.

Pagina 127

17Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-5. Preferences tab3.4.5 Fluid selection for database

Pagina 128 - Symptom Corrective Action

18Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNote The following example will show a flow configuration for

Pagina 129

19Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration7. Verify that the Reference Conditions are correct for the a

Pagina 130

20Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.4.6 Fluid properties NoteThe Fluid Properties tab is an opti

Pagina 131 - Reference Data

21Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.4.7 Primary element selectionThe Primary Element Selection

Pagina 132 - Total performance

22Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationContinuing with the example configuration:1. Expand the Condit

Pagina 133 - Warranty

23Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteTo be in compliance with appropriate national or internat

Pagina 134 - Ambient Temperature effect

iReference Manual 00809-0100-4803, Rev DATable of ContentsApril 2013Table of Contents 1Section 1: Introduction1.1 Using this manual. . . . . . . . . .

Pagina 135 - Vibration effect

24Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteThe user will be notified if the configuration has been mo

Pagina 136 - Power supply effect

25Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteAfter the configuration is sent to the device, saving the

Pagina 137 - Range and sensor limits

26Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.4.9 Other fluid configurationsNatural gasNatural gas AGA No.

Pagina 138 - 4–20 mA/HART

27Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteThese percent composition values should add to 100%. If t

Pagina 139 - Static Pressure limit

28Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration5. If appropriate, enter the optional data for the Natural Gas

Pagina 140 - Humidity limits

29Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration10. Click Next to continue with the flow configuration on the

Pagina 141 - Failure mode alarm

30Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration8. Enter the Custom Liquid Viscosity at the given temperatures

Pagina 142 - A.1.3 Physical specifications

31Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.5 Basic device configurationThis section provides procedure

Pagina 143 - Cover O-rings

32Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-16. Basicsetup tab1. Verify the Device Tag informatio

Pagina 144

33Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteBoth absolute and gage pressure are available as variable

Pagina 145 - A.2 Dimensional drawings

iiReference Manual 00809-0100-4803, Rev DATable of ContentsApril 2013Table of Contents3.4 Flow configuration. . . . . . . . . . . . . . . . . . . . .

Pagina 146 - Pipe Mount Panel Mount

34Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.6 Detailed device configuration 3.6.1 Model identificationTh

Pagina 147 - Appendix A: Reference Data

35Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTable 3-4. Rosemount (standard) alarm and saturation valuesT

Pagina 148 - (90 Max open)

36Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationAlarm level verificationThe transmitter alarm level should be

Pagina 149 - A.3 Ordering information

37Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-19. Device - variable mapping tab3.6.4 LCD displayTh

Pagina 150

38Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-20. Device - LCD tab3.6.5 Communication setupThe Comm

Pagina 151

39Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-21. Device - comm setup tabBurst modeWhen Burst Mode

Pagina 152 - 2 SST flange adapter

40Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationChoosing a burst optionThis parameter selects the information

Pagina 153

41Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-22. Typical multidrop networkEnable multidrop commun

Pagina 154

42Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-23. Device - materials of construction tab3.6.7 Flow

Pagina 155

43Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.7 Variable configuration 3.7.1 Flow rate (Fully Compensated

Pagina 156

iiiReference Manual 00809-0100-4803, Rev DATable of ContentsApril 2013Table of Contents4.2.1 Warnings . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 157 - A.4 Accessories

44Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteIf the flow rate is configured as the primary variable and

Pagina 158 - A.5 Exploded view diagram

45Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTable 3-9. Common custom units - FlowIf conversion factor ta

Pagina 159 - A.6 Spare Parts

46Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTo calculate the Base per Custom value for a custom unit not s

Pagina 160

47Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTime conversion example:To find the Base per Custom relations

Pagina 161

48Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationMass/volume and time conversion example:To find the Base per C

Pagina 162

49Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.7.2 Energy rate(Fully Compensated Mass and Energy Flow Feat

Pagina 163

50Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationExample:Custom Unit: kgBase Unit: gBecause 1 kg (Kilogram) = 1

Pagina 164

51Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTo calculate the Base per Custom value for a custom unit not

Pagina 165

52Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-29. Energy rate custom uUnits - Energy conversion exa

Pagina 166 - European certifications

53Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-30. Energy rate custom units - Time conversion examp

Pagina 167 - Japanese certifications

ivReference Manual00809-0100-4803, Rev DATable of ContentsApril 2013Table of ContentsA.1.2 Functional specifications. . . . . . . . . . . . . . . . .

Pagina 168 - China (NEPSI) certifications

54Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationEnergy and time conversion example:To find the Base per Custom

Pagina 169 - IECEx certifications

55Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.7.3 Totalizer(Fully Compensated Mass and Energy Flow Featur

Pagina 170

56Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNoteIf the totalizer rate is configured as the primary variabl

Pagina 171 - B.5 Installation drawings

57Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTable 3-11. Common custom units - Totalizer If conversion fa

Pagina 172 - Product Certifications

58Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-33. Totalizer custom units - Totalizer example3.7.4 D

Pagina 173

59Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration1. Under the Differential Pressure Setup heading, edit the DP

Pagina 174

60Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationNote The transmitter may be equipped with either an absolute o

Pagina 175

61Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTable 3-12. Temperature modesNoteProcess Temperature Mode Se

Pagina 176

62Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-37. Variables - module temperature tab1. Under the Mo

Pagina 177

63Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-38. Variables - analog output tab1. Select the Prima

Pagina 178

1Reference Manual 00809-0100-4803, Rev DASection 1: IntroductionApril 2013IntroductionSection 1 IntroductionUsing this manual . . . . . . . . . . . .

Pagina 179

64Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationFigure 3-39. Square root output transition pointFigure 3-39 on

Pagina 180

65Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.8.1 Menu tree for fully compensated mass and energy flow (p

Pagina 181 - B.5.3 GE / GM option NEMA 4X

66Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.8.2 Menu tree for fully compensated mass and energy flow (pa

Pagina 182

67Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.8.3 Menu tree for direct process variable output (page 1)1.

Pagina 183

68Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.8.4 Menu tree for direct process variable output (page 2)1.

Pagina 184

69Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration3.8.5 475 Fast keysUse 3051SMV Engineering Assistant or any H

Pagina 185

70Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationLoop Test 1,2,2Module Temperature Reading and Status 1,4,2,1,8

Pagina 186

71Reference Manual 00809-0100-4803, Rev DASection 3: ConfigurationApril 2013ConfigurationTable 3-14. Fast keys for direct process variable measuremen

Pagina 187

72Reference Manual00809-0100-4803, Rev DASection 3: ConfigurationApril 2013Configuration⻫Status 1,2,1⻫Tag 1,3,1⻫Transfer Function 1,3,6Variable Mappin

Pagina 188

Reference Manual 00809-0100-4803, Rev DASection 4: Operation and MaintenanceApril 20139Operation and MaintenanceSection 4 Operation and MaintenanceOv