Transmitter Configuration and Use: Series 1000 and 2000 Transmitters 21
Connecting with ProLink II Software continued
Using the Display Using the CommunicatorUsing ProLink IIBefore You Begin
7. If an error message appears:
a. Swap the leads between the two terminals and try again.
b. Ensure you are using the correct COM port.
c. If you are in RS-485 mode, you may be using incorrect connection parameters.
- Connect using the service port and check the RS-485 configuration. If required,
change the configuration or change your RS-485 connection parameters to match the
existing configuration.
- If you are unsure of the transmitter’s address. use the
Poll button in the Connect
window to return a list of all devices on the network.
d. Check all the wiring between the PC and the transmitter.
3.5.2 HART/Bell202 connections
HART/Bell202 connections are made through terminals 21 and 22. See Figure 3-9.
Figure 3-9 HART/Bell202 connections to Model 1500 or 2500
CAUTION
Connecting a HART device to the transmitter’s
primary mA output terminals could cause transmitter
output error.
If the primary mA output is being used for flow control,
connecting a HART interface to the output loop could
cause the transmitter’s 4–20 mA output to change, which
would affect flow control devices.
Set control devices for manual operation before
connecting a HART interface to the transmitter’s primary
mA output loop.
VIATOR
250–600 Ω