36 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Flowmeter Startup continued
Figure 5-5 ProLink II – mA output trim procedure
Calibration
ProLink Menu
Read mA output at
receiving device
Equal?
Enter receiving device
value in
Enter Meas
Read mA output at
receiving device
Milliamp Trim 1
Milliamp Trim 2
No Yes
OK
Do Cal
Read mA output at
receiving device
Equal?
Enter receiving device
value in
Enter Meas
Read mA output at
receiving device
No
Do Cal
DONE
4 mA trim 20 mA trim
OK
Yes