90 Transmitter Configuration and Use: Series 1000 and 2000 Transmitters
Optional Configuration continued
Example 1
Configuration:
Flow direction = Forward only
mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the first graph in Figure 8-1.)
As a result:
Under conditions of reverse flow or zero flow, the mA output level
is 4 mA.
Under conditions of forward flow, up to a flow rate of 100 g/s, the
mA output level varies between 4 mA and 20 mA in proportion to
(the absolute value of) the flow rate.
Under conditions of forward flow, if (the absolute value of) the flow
rate equals or exceeds 100 g/s, the mA output will be proportional
to the flow rate up to 20.5 mA, and will be level at 20.5 mA at
higher flow rates.
Example 2
Configuration:
Flow direction = Reverse only
mA output: 4 mA = 0 g/s; 20 mA = 100 g/s
(See the second graph in Figure 8-1.)
As a result:
Under conditions of forward flow or zero flow, the mA output level
is 4 mA.
Under conditions of reverse flow, up to a flow rate of 100 g/s, the
mA output level varies between 4 mA and 20 mA in proportion to
the absolute value of the flow rate.
Under conditions of reverse flow, if the absolute value of the flow
rate equals or exceeds 100 g/s, the mA output will be proportional
to the absolute value of the flow rate up to 20.5 mA, and will be
level at 20.5 mA at higher absolute values.