Reference Manual
00809-0100-4803, Rev DA
Appendix A: Reference Data
April 2013
Specifications and Reference Data
Turn-On time
Performance within specifications less than 5 seconds for 3051SMV (typical) after power is
applied to the transmitter.
Volumetric displacement
Less than 0.005 in
3
(0,08 cm
3
)
Damping
Analog output response to a step change is user-selectable from 0 to 60 seconds for one time
constant. Each variable can be individually adjusted. This software damping is in addition to
sensor module response time.
Failure mode alarm
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven offscale to
alert the user. Rosemount standard (default), NAMUR, and custom alarm levels are available
(see Tab le A -1 below).
High or low alarm signal is software-selectable or hardware-selectable via the optional switch
(option D1).
Table A-1. Alarm configuration
High Alarm Low Alarm
Default 21.75 mA 3.75 mA
NAMUR compliant
(1)
(1) Analog output levels are compliant with NAMUR recommendation NE 43, see option codes C4 or C5.
22.5 mA 3.6 mA
Custom levels
(2)
(2) Low alarm must be 0.1 mA less than low saturation and high alarm must be 0.1 mA greater than high
saturation.
20.2 - 23.0 mA 3.6 - 3.8 mA