Section 4: Operation and Maintenance
April 2013
Operation and Maintenance
Note
Select process variable calibration input values so that low and high values are equal to or
outside the upper and lower range limits. Do not attempt to obtain reverse output by reversing
the high and low points. The transmitter allows approximately five percent URL deviation from
the characterized curve established at the factory.
Calibration type
The calibration type drop-down menu allows the user to note the type of device last used to
calibrate the sensor (either Differential, Gage, or Absolute). This field does not affect the
calibration of the device.
Recall factory trim
The Recall Factory Trim button will restore the transmitter to the original factory characteriza-
tion curve. The Recall Factory Trim button can be useful for recovering from an inadvertent zero
trim or inaccurate pressure source.
When the recall factory trim function is used, the transmitter’s upper and lower trim values are
set to the values configured at the factory. If custom trim values were specified when the
transmitter was ordered, the device will recall those values. If custom trim values were not
specified, the device will recall the upper and lower sensor limits.
Last DP sensor trim point
The current upper and lower trim points can be seen under the Last DP Sensor Trim Point heading.
4.3.4 Static pressure sensor calibration
The Static Pressure Calibration Tab allows the user to complete either a zero trim procedure or a
full SP sensor trim, see Figure 4-3.
Mass and Energy Flow Fast Keys 1, 2, 5, 4
Direct Process Var. Output Fast Keys 1, 2, 4, 4