Reference Manual
00809-0100-4803, Rev DA
Section 4: Operation and Maintenance
April 2013
Operation and Maintenance
4.4.2 Configuring fixed process variables
Under the Fixed Process Variables heading, the user may temporarily set the Differential Pressure,
Static Pressure or Process Temperature to a user defined fixed value for testing purposes. Once
the user leaves the Configure Fixed Variable method, the fixed process variable will be
automatically returned to a live process variable measurement.
4.4.3 Analog output loop test
Under the Analog Output Verify heading, a Loop Test can be performed by clicking the Loop Test
button. The loop test command verifies the output of the transmitter, the integrity of the loop,
and the operations of any recorders or similar devices installed in the loop.
4.5 Process variables
4.5.1 Process variable tabs
The Process Variables screen shows a graphical representation of the respective variable. An
example of the Primary Variable tab is shown in Figure 4-7. The chart on these Process Variables
tabs will begin plotting when the user first navigates to the screen, and will only continue
plotting while the user is viewing this tab. The user may view a larger version of the chart by
clicking on the Large Chart button.
Each of the four digital output variables has a screen similar to the one shown in Figure 4-7.
Mass and Energy Flow Fast Keys 1, 2, 4
Direct Process Var. Output Fast Keys 1, 2, 3
Mass and Energy Flow Fast Keys 1, 2, 2
Direct Process Var. Output Fast Keys 1, 2, 2
Mass and Energy Flow Fast Keys 1, 1
Direct Process Var. Output Fast Keys 1, 1