Stan dard fea tures - all sys tems (con tin ued)
Warranty clauses
The warranty does not cover any damage or malfunction of
the unit which may occur during or as a result of operating the
unit outside of the specified application limits.
Liebert does not accept responsibility for any damage caused
by improper use of the product.
Operating limits
Intelecool EX units are designed for operation within the
following working limits (the limits are applicable to newly
commissioned machines which have been correctly installed
and maintained).
Mod els LEX04/05/06E
Power Sup ply:
230 Vac ± 10%/1/50 Hz
48±20% VDC (with the emer gency cool ing option)
24±20% VDC (with the emer gency cool ing option)
Mod els LEX08/10/14E
Power Sup ply:
400 Vac ± 10%/3/50 Hz
All mod els
External ambient:
From -25 °C (with fan speed control) to 50 °C (48 °C for
models LEX06E and LEX14E)
Internal ambient:
From 20 °C, (30% to 80% R.H.) to 32 °C, 40% R.H.
Storage conditions:
From -40°C, 5% R.H. to 55 °C, 90% R.H.
SLE ICX TDM E.2 (06/99) 5