Tech ni cal data - LEX05E
DX Ca pac ity (50Hz)*
Out door tem pera ture [°C]
25 30 35 40 45
In door con di tion: 21°C, 50% r.h.
Total cooling capacity kW 5.1 4.9 4.7 4.5 4.4
Sensible cooling capacity kW 4.5 4.5 4.4 4.3 4.2
Compressor absorbed power kW 1.2 1.3 1.5 1.6 1.8
Compressor absorbed current A 5.4 5.7 6.2 6.8 7.6
In door con di tion: 24°C, 50% r.h.
Total cooling capacity
kW 5.5 5.3 5.1 4.9 4.8
Sensible cooling capacity
kW 4.7 4.6 4.6 4.5 4.4
Compressor absorbed power
kW 1.3 1.4 1.5 1.7 1.8
Compressor absorbed current
A 5.6 5.9 6.3 7.0 7.8
In door con di tion: 27°C, 47% r.h.
Total cooling capacity kW 5.8 5.6 5.5 5.2 5.0
Sensible cooling capacity kW 5.0 5.0 4.9 4.8 4.8
Compressor absorbed power kW 1.3 1.4 1.5 1.7 1.8
Compressor absorbed current A 5.7 6.0 6.4 7.1 7.9
In door con di tion: 30°C, 40% r.h.
Total cooling capacity kW 6.0 5.7 5.6 5.4 5.2
Sensible cooling capacity kW 5.8 5.7 5.6 5.4 5.2
Compressor absorbed power kW 1.3 1.4 1.5 1.7 1.9
Compressor absorbed current A 5.8 6.1 6.5 7.3 8.2
Free cool ing Ca pac ity
Out door tem pera ture [°C]
10 15 20
In door tem pera ture: 21°C
Sensible cooling capacity
kW 5.1 2.8 0.5
In door tem pera ture: 24°C
Sensible cooling capacity kW 6.6 4.2 1.9
In door tem pera ture: 27°C
Sensible cooling capacity
kW 8.0 5.6 3.3
In door tem pera ture: 30°C
Sensible cooling capacity kW 9.4 7.0 4.7
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engine ers.
Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE ICX TDM E.2 (06/99) 11
In tele Cool EX - Tech ni cal Data Man ual
Comentarios a estos manuales