Optional fea tures - all sys tems
Electric heater
The heater option is available for all models. Models
LEX04E, LEX05E, and LEX06E are supplied with two
heater elements for a total capacity of 3 kW. Models
LEX08E, LEX10E, and LEX14E are supplied with two
heater elements for a total capacity of 6 kW.
Heater control is of the ON-OFF type. The heater is provided
with a manual reset, heater safety thermostat, to disable the
heater in the event of high temperature.
The heater safety thermostat also incorporates a
magneto-thermal switch which protects the heater from short
circuits, should the cable harness be damaged accidentally.
Re duced kW heat ers
A further heater option is available to special order, when the
power supply to the unit is limited. Reduced heater capacity is
1.5 kW for LEX04E, LEX05E and LEX06E and 3.0 kW for
LEX08E, LEX10E and LEX14E.
External inverter kit
The electric panel is configured for connection to an external
inverter (output 230V or 400VAC, not supplied by Liebert).
This allows emergency operation of the AC evaporator fans,
controller and the Freecooling damper in case of mains power
failure.
Voltage failure relay
The voltage failure relay can be used to generate an alarm in
case of mains power loss or when the main circuit breaker
(MCB) is open.
R407C
An optional “Zero ODP” refrigerant, R407C is available with
the unit. Cooling capacities and electrical consumption are
within 5% of the stated capacities for R22.
Emergency cooling
The unit can be supplied with an emergency cooling system
that allows the indoor fans, the controller and the motor
damper to run from a 48V or 24 V DC power supply. This
allows the unit to maintain air circulation inside the room in
the event of mains power failure.
For the emergency cooling option, the standard evaporator
fans are replaced by two free wheel fans with backward
curved blades, each driven by a DC motor. The DC supply is
provided by 24V or 48V batteries located inside the
conditioned space.
With this option, the evaporator fans, the controller and the
damper actuator are permanently powered from a battery DC
supply. The other components, compressor, reheat etc. are
mains powered. In the event of mains failure, these other
components will not operate.
Grilles
Air inlet and discharge grilles and connection ducts are also
available. The grilles are manufactured with extruded
aluminium (natural anodised finishing) with a single row of
adjustable fins. Metallic ducts are especially designed to
prevent water entering the site through the unit.
Special packaging
Where the unit is to be transported by sea or in other cases
where heavy duty packaging is required, special crating is
available.
This can consist of either a wooden crate over the standard
carboard/bubble wrap packaging or the entire unit can be
encased in a wooden box complete with silicon desiccant.
High ambient operation
If the unit is to be used in applications where the outside
ambient is higher than 45
o
C, performance will be derated
from the catalogue values. Consult Liebert Applications
Engineers for recommendations on use of the unit outside the
specified operating limits.
The maximum recommended ambient temperature for
standard units operating with R22 or R407C is 50
0
C for
LEX04E, LEX05E, LEX08E and LEX10E and 48
0
C for
LEX06E and LEX14E.
TXV on mod els LEX04/05/06E
An externally equalised, adjustable, thermostatic expansion
valve is available as a special option on models
LEX04/05/06E. It is recommended for high ambient
operations.
6 SLE ICX TDM E.2 (06/99)
InteleCool EX - Technical Data Manual