Stan dard fea tures - all sys tems
Cabinet
The cabinet is manufactured from zinc coated steel, it is then
de-greased and painted in “Pearl White” (RAL7032) dry
powder epoxy resin paint. The paint finish is easily cleaned
and is hard wearing.
The cabinet has been designed specifically for outdoor
applications, all materials, fittings and components have been
selected to provide maximum weather protection, durability
and security (vandal-proof cabinet). The unit has removable
panels (a special key is required) which give access to all
internal components.
The condenser air inlet is through metallic grilles at the side
of the unit. Condenser air outlet is from the bottom of the front
panel. A metal safety grid prevents accidental contact with
the fan and the coil. The compressor is located in the bottom of
the unit. The panels are insulated with 10 mm, 70 kg/m
3
density, mineral wool.
Refrigeration circuit
The units are single circuit with a hermetic compressor (rotary
on models LEX04/05/06E, scroll on models LEX08/10/14E).
The circuit incorporates a thermostatic expansion valve
(capillary tube on models LEX04/05/06E) which controls the
refrigerant flow to the evaporator. A filter dryer is provided in
the liquid line to eliminate moisture from the system and
maximum efficiency for increased working life.
The compressor has a manual-reset high pressure switch for
high pressure protection and a high pressure alarm circuit to
warn of high system pressures, allowing corrective action to
be taken before a significant loss of temperature control
occurs. The low pressure switch is auto-resetting and detects
low pressure conditions such as loss of refrigerant charge. The
low-pressure switch incorporates a delay for winter start
operation.
Crank case heat ers
Crankcase heaters are standard on all models. They maintain
minimum refrigerant temperature and are energised while the
unit is powered and the compressor is off.
Evaporator section
Evapo ra tor coil
The evaporator coil is constructed from copper tubes with
aluminium fins to ensure maximum heat transfer. It is
designed to maximise the available surface area resulting in
low face velocities, low internal air pressure drops and the
high sensible heat ratios. A corrosion resistant drain pan is
provided on all models.
Evapo ra tor fan mo tor
The units are equipped with two centrifugal fans with forward
curved impellers, housed in galvanised steel. A single
double-shafted motor is directly coupled to the two fans
(Model LEX14E has two direct drive fan motors). The fan
impellers are statically and dynamically balanced and
equipped with self-lubricating bearings. The fan is mounted
on vibration-absorbing rubber supports to reduce vibration
transmission between the fan and the unit frame. This
vibration attenuation helps to keep noise emission to a
minimum.
The fan motor is single-phase, IP44 rated and complete with
internal thermal protection.
Condenser section
Con denser coil
The condenser coil is constructed from copper tubes with
aluminium fins to ensure maximum heat transfer. It is
designed to maximise the available surface area resulting in
low face velocities and low internal air pressure drops.
Con denser fan
The condenser section is equipped with a single axial fan with
integral motor. It is also statically and dynamically balanced.
The fan impeller and casing are made from zinc-coated steel
to protect against corrosion. The direct drive motor includes
sealed-for-life bearings. The fan motor is IP54 rated and
complete with internal thermal protection. The fan motor is
controlled by a pressure switch to maintain a steady
condensing temperature.
Fan speed con trol ler
A factory fitted solid state fan speed controller is installed to
maintain the refrigerant condensing pressure. The controller
varies airflow through the condenser to maintain a constant
pressure. The advantages of fan speed control are two-fold.
Higher reliability of the system due to less starts/stops of the
compressor and a lower noise level because the fan is running
at a lower speed, mainly during night time.
SLE ICX TDM E.2 (06/99) 3
InteleCool EX - Technical Data Manual
Comentarios a estos manuales