Emerson Liebert InteleCool 2 Manual de usuario Pagina 22

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 30
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 21
Elec tri cal data - all mod els (continued)
Mains dis con nect switch and ca bling rec om men da tions *
VER SION
MCB (Dif fer en tial cur rent = 0.3 A)
Ca ble siz ing
230V/1/50Hz 400V/3/50Hz
Cooling Only
LEX04/05/06E 20A -
2 x 4 mm
2
Earth x 4 mm
2
LEX08/10/14E - 20A
4 x 4 mm
2
Earth x 4 mm
2
Cooling/
Heating
LEX04/05/06E 20A -
2 x 4 mm
2
Earth x 4 mm
2
LEX08/10/14E - 20A
4 x 4 mm
2
Earth x 4 mm
2
Cooling/
Heating/
Freecooling
LEX04/05/06E 20A -
2 x 4 mm
2
Earth x 4 mm
2
LEX08/10/14E - 20A
4 x 4 mm
2
Earth x 4 mm
2
VER SION
MCB (Dif fer en tial cur rent = 0.3 A)
Ca ble siz ing
24V DC 48V DC
Emergency cooling
LEX04/05/06E
10A 16A 2 x 2.5 mm
2
LEX08/10/14E
- - 2 x 2.5 mm
2
* Recommenations only, superceded by local and national codes and regulations.
18 SLE ICX TDM E.2 (06/99)
In tele Cool EX - Tech ni cal Data Man ual