Tech ni cal data - LEX08E
DX Ca pac ity (50Hz)*
Out door tem pera ture [°C]
25 30 35 40 45
In door con di tion: 21°C, 50% RH
Total cooling capacity kW 7.5 7.5 7.2 7.0 6.8
Sensible cooling capacity kW 7.5 7.5 7.2 7.0 6.8
Compressor absorbed power kW 1.4 1.5 1.7 1.9 2.1
Compressor absorbed current A 2.9 3.0 3.2 3.5 3.9
In door con di tion: 24°C, 50% RH
Total cooling capacity
kW 8.1 7.9 7.8 7.6 7.2
Sensible cooling capacity
kW 8.1 7.9 7.8 7.6 7.2
Compressor absorbed power
kW 1.4 1.5 1.7 1.9 2.1
Compressor absorbed current
A 3.1 3.1 3.2 3.5 3.9
In door con di tion: 27°C, 47% RH
Total cooling capacity kW 8.7 8.5 8.2 8.0 7.8
Sensible cooling capacity kW 8.7 8.5 8.2 8.0 7.8
Compressor absorbed power kW 1.4 1.5 1.7 1.9 2.1
Compressor absorbed current A 3.1 3.1 3.2 3.5 3.9
In door con di tion: 30°C, 40% RH
Total cooling capacity kW 9.2 9.0 8.7 8.5 8.2
Sensible cooling capacity kW 9.2 9.0 8.7 8.5 8.2
Compressor absorbed power kW 1.4 1.5 1.7 1.9 2.2
Compressor absorbed current A 3.0 3.1 3.3 3.6 3.6
Free cool ing Ca pac ity
Out door tem pera ture [°C]
10 15 20
In door tem pera ture: 21°C
Sensible cooling capacity
kW 7.8 4.3 0.7
In door tem pera ture: 24°C
Sensible cooling capacity kW 10.0 6.4 2.8
In door tem pera ture: 27°C
Sensible cooling capacity
kW 12.1 8.5 5.0
In door tem pera ture: 30°C
Sensible cooling capacity kW 14.2 10.7 7.1
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engine ers.
Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE ICX TDM E.2 (06/99) 13