Tech ni cal data - LEX10E
DX Ca pac ity (50Hz)*
Out door tem pera ture [°C]
25 30 35 40 45
In door con di tions: 21°C, 50% r.h.
Total cooling capacity kW 10.0 9.7 9.3 9.0 8.8
Sensible cooling capacity kW 9.4 9.3 9.1 9.0 8.8
Compressor absorbed power kW 2.1 2.3 2.5 2.8 3.0
Compressor absorbed current A 3.9 4.2 4.6 4.9 5.3
In door con di tions: 24°C, 50% r.h.
Total cooling capacity
kW 10.8 10.5 10.1 9.7 9.4
Sensible cooling capacity
kW 9.7 9.6 9.5 9.3 9.2
Compressor absorbed power
kW 2.1 2.3 2.5 2.8 3.1
Compressor absorbed current
A 4.0 4.3 4.6 5.0 5.4
In door con di tions: 27°C, 47% r.h.
Total cooling capacity kW 11.3 11.0 10.7 10.4 9.9
Sensible cooling capacity kW 10.4 10.3 10.2 10.1 9.9
Compressor absorbed power kW 2.1 2.3 2.6 2.8 3.1
Compressor absorbed current A 4.0 4.3 4.6 5.0 5.4
In door con di tions: 30°C, 40% r.h.
Total cooling capacity kW 11.9 11.5 11.2 10.9 10.5
Sensible cooling capacity kW 11.9 11.5 11.2 10.9 10.5
Compressor absorbed power kW 2.1 2.4 2.6 2.8 3.1
Compressor absorbed current A 4.0 4.3 4.7 5.1 5.4
Free cool ing Ca pac ity
Out door tem pera ture [°C]
10 15 20
In door tem pera ture: 21°C
Sensible cooling capacity
kW 7.8 4.3 0.7
In door tem pera ture: 24°C
Sensible cooling capacity kW 10.0 6.4 2.8
In door tem pera ture: 27°C
Sensible cooling capacity
kW 12.1 8.5 5.0
In door tem pera ture: 30°C
Sensible cooling capacity kW 14.2 10.7 7.1
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engine ers.
Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
14 SLE ICX TDM E.2 (06/99)