Elec tri cal data - all mod els
Stan dard fea tures
Model
Power
Sup ply
Evapo ra tor fan Elec tric heat ing (opt.)
OA FLA LRA
Rated Power
[kW]
FLA
Rated Power
[kW]
LEX04E 230/1/50 1.1 1.2 1.75 0.2 13.1 3
LEX05E 230/1/50 1.1 1.2 1.75 0.2 13.1 3
LEX06E 230/1/50 1.1 1.2 1.75 0.2 13.1 3
LEX08E
400/3/50 3.2 5.0 - 0.7 8.70 6
LEX10E
400/3/50 3.2 5.0 - 0.7 8.70 6
LEX14E
400/3/50 2.5x2 3.6x2 - 0.6 x 2 8.70 6
Model
Power
Sup ply
Con denser fan Com pres sor (R22)
OA FLA LRA
Rated
Power
[kW]
OA
+
FLA LRA
Rated
Power
[kW]
LEX04E 230/1/50 1.3 1.4 3.0 0.3 5.9 10 34 1.4
LEX05E 230/1/50 1.3 1.4 3.0 0.3 7.1 12 37 1.7
LEX06E 230/1/50 1.3 1.4 3.0 0.3 8.8 15 48 2.0
LEX08E 400/3/50 3.4 3.5 7.4 0.8 3.9 4.8 31 2.1
LEX10E 400/3/50 3.4 3.5 7.4 0.8 5.3 6.6 43 3.0
LEX14E 400/3/50 3.4 3.5 7.4 0.8 8.5 12.4 65 4.7
+
Compressor Operating Amps are quoted at 55
0
C condensing temperature.
Op tional fea tures
Model
Evapo ra tor fan mo tor 48 Vdc
(2 units)*
Evapo ra tor fan mo tor 24 Vdc
(2 unit)**
FLA [A] Rated Power [Watts] FLA [A] Rated power [Watts]
LEX04E
2.7 x 2 70 x 2 5.4 x 2 102 x 2
LEX05E 2.7 x 2 70 x 2 5.4 x 2 102 x 2
LEX06E 2.7 x 2 70 x 2 5.4 x 2 102 x 2
LEX08E NA NA NA NA
LEX10E NA NA NA NA
LEX14E NA NA NA NA
OA = Absorbed current, in standard operation. FLA = Full Load Amps, LRA = Locked Rotor Amps
NA = Not available at the current time. This feature will be available in the near future, consult Liebert Applications Engineers
* With emergency cooling 48 Vdc option
** With emergency cooling 24 Vdc option