CHAPTER 2.
INSTALLING THE SYSTEM
GENERAL REQUIREMENTS
The shelf is designed for mounting in a 19-inch or 23-inch wide relay rack with 1-3/4
inch multiple drilling.
The installer should be familiar with the installation requirements and techniques to
be used in securing the shelf(s) to a relay rack.
This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product must be located in a Controlled Environment with access to
Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO,
vault, hut, or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a
Network Telecommunication Facility (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the
front of the relay rack and 2' for the rear of the relay rack.
Converter module and mounting shelf ventilating openings must not be blocked and
temperature of air entering system must not exceed rated Operating Ambient
Temperature Range found in SAG584622100.