Installation and User Instructions UM584622100
Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375) Issue AC, July 3, 2012
Chapter 3. Setting Jumper and Switch Options Page 13
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Jumper P2
Jumper P2 is the CAN termination jumper.
a) When in stand alone mode, the jumper P2 must be in place to ensure reliable
communications.
b) When an ACU+ is on the CAN bus, jumper P2 should be removed.
Inside View of Main Shelfs Front Door
TB1
1 9 1 12
TB2P2
Jumper
P2
Switch
S1
S1
OFF
ON
4 3 2 1
Figure 3-1
System Interface Circuit Card Jumper and Switch Locations