UM584622100 Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Page 8 Chapter 2. Installing the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INSTALLING BULLET NOSE CIRCUIT BREAKERS
AND/OR FUSEHOLDERS (WITH TPS/TPL FUSES)
Caution: For ambient temperatures at or below +40°C (+104°F), overcurrent
devices rated 100A or greater MUST HAVE an empty mounting position
between it and any other overcurrent protective device. Maximum size
circuit breakers that can be used are 100A single pole, 200A double pole,
and 250A triple pole. Maximum size fuse is 100A. The distribution row is
rated for a maximum of 250A.
For ambient temperatures between +40°C (+104°F) and +65°C (+149°F),
overcurrent devices rated 60A or greater MUST HAVE an empty
mounting position between it and any other overcurrent protective
device. Maximum size circuit breakers that can be used are 70A single
pole. No double pole or triple pole circuit breakers can be used.
Maximum size fuse 70A. The distribution row is rated for a maximum of
250A.
Note: Circuit breakers and/or fuses may have been factory installed for you. If so, verify
their positions and sizes.
Procedure
1) Open the shelf’s front door.
2) Circuit Breakers and Fuses: Ensure that a circuit breaker is in the OFF
position. Orient the distribution device as shown in Figure 2-5. Insert the
terminals on the rear of the distribution device into their corresponding sockets
on the distribution row. Ensure the alarm contact on the back of the distribution
device makes contact with the alarm terminal on the mounting circuit card. Push
distribution device in firmly until fully seated in the distribution row.
3) Fuses: When all fuseholders are installed, install an appropriately sized
TPS/TLS fuse in each. To do this, remove the fuse carrier from the mounted
fuseholder body by pulling it straight out. Slide the fuse in place between the
contacts of the fuse carrier. When done, push the fuse carrier back into the
fuseholder body. Note that a polarizing key on the bottom of the carrier prevents
the carrier from being inserted upside down. Verify that an 18/100 ampere alarm
fuse is present in each fuseholder and that a plastic safety cover is installed on
this fuse.
4) Record all circuit breaker and/or fuse sizes on the label provided.
5) Close the shelf's front door.