UM584622100 Installation and User Instructions
Issue AC, July 3, 2012 Spec. Nos. 584622100, 584622200, 584622300, 584622400 (Model DCS48375)
Page 24 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
DC Input Connections
* 3/8-16 x 0.875studs on 1centers
for installation of leads with 2-hole lugs.
* Provide separate inputs for each converter.
* Maximum lug width 0.812.
* Torque to 240 in-lbs.
+24VDC
Converter #1 (top)
Converter #2
Converter #3
Converter #4 (bottom)
DC Input Leads
Enter Here
Return
Converter #1 (top)
Converter #2
Converter #3
Converter #4 (bottom)
Rear panels removed in illustration.
Rear
Dual Converter Module Feed
with Adapter Busbars
P/Ns 552506
Feed Two
Feed One
+24VDC
Converter #3
Converter #4
Return
Converter #3
Converter #4
+24VDC
Converter #1
Converter #2
Return
Converter #1
Converter #2
Rear
DC Input Connections
* 3/8-16 x 0.875studs on 1centers
for installation of leads with 2-hole lugs.
* Provide one input for two converters.
* Maximum lug width 1.156.
* Torque to 240 in-lbs.
Discard Extra Hardware
Busbars
P/Ns 552506
584622100 / 584622200 shown.
584622300 / 584622400 similar.
Figure 4-7
DC Input Connections